Smartgen HGM7110DC User Manual page 48

Dc genset controller
Table of Contents

Advertisement

17
Auto Mode Lock
18
Auto Mode Invalid
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
22
Aux Instrument Mode
23
Reserved
24
Reset Maintenance
25
Reserved
26
Aux. High Temp
27
Aux. Low OP
Remote Start
28
(On Load)
29
Reserved
30
Aux. Manual Start
31
1#Acc.Charge Closed
32
2#Acc.Charge Closed
33
Simulate Stop key
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
37
Simulate Start key
38
Simulate Gen Load key
39
Reserved
40
Reserved
41
Reserved
42
Reserved
43
Simulate Raise Key
HGM7110DC Genset Controller
Accumulator.
When input is active, controller enters into Auto Mode;
all the keys except
in the right of first row in LCD.
When input is active, controller won't work under Auto
Mode.
key and simulate auto key input does not
work.
All shutdown alarms are prohibited except emergence
stop.(i.e. battle mode or override mode)
All outputs are prohibited in this mode.
Controller will set maintenance time and date as default
when input is active.
Connect to sensor digital input.
Connect to sensor digital input.
In Auto mode, when input is active, can start genset
automatically and with load when genset is normal
running; when input is inactive, can stop genset
automatically.
In Manual mode, when input is active, can start genset
automatically; when input is inactive, can stop genset
automatically.
Connect to the auxiliary point of 1# accumulator.
Connect to the auxiliary point of 2# accumulator.
An external button; can be connected to simulate panel
button.
An external button; can be connected to simulate panel
Version: 1.0
HGM7110DC Genset Controller
are inactive and there is
2014-09-27
Page 48 of 68