Smartgen HGM7110DC User Manual page 39

Dc genset controller
Table of Contents

Advertisement

No.
Items
Configure Input Ports
Configure Input 1
Contents
1
Setting
2
Active Type
Configure Input 2
Contents
1
Setting
2
Active Type
Configure Input 3
Contents
1
Setting
2
Active Type
Configure Input 4
Contents
1
Setting
2
Active Type
3
Arming
4
Active Actions
5
Active Delay
6
Description
Configure Input 5
Contents
1
Setting
2
Active Type
3
Arming
4
Active Actions
5
Active Delay
HGM7110DC Genset Controller
Parameters
Defaults
(0-50)
28
(0-1)
0
(0-50)
26
(0-1)
0
(0-50)
27
(0-1)
0
(0-50)
0
(0-1)
0
(0-3)
2
(0-4)
0
(0-20.0)s
2.0
(0-50)
0
(0-1)
0
(0-3)
2
(0-4)
1
(0-20.0)s
2.0
Version: 1.0
HGM7110DC Genset Controller
Description
Remote start (on load). See form 3
0: Closed to active
1: Open to active
High temperature shutdown
See form 3
0: Closed to active
1: Open to active
Low oil pressure shutdown
See form 3
0: Closed to active
1: Open to active
User defined. See form 3
0: Closed to active
1: Open to active
0: From safety on 1: From starting
2: Always 3:Never
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
Time from detecting active to confirm
LCD display detailed contents when
the input is active.
User defined .See form 3
0: Closed to active
1: Open to active
0: From safety on 1: From starting
2: Always 3:Never
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
Time from detecting active to confirm
2014-09-27
Page 39 of 68