Smartgen HGM7110DC User Manual page 34

Dc genset controller
Table of Contents

Advertisement

No.
Items
GOV
Volt.
31
Max.
GOV Interface
32
Type
33
GOV Gain
34
GOV Stability
35
GOV Kd
36
AVR Volt. Min.
37
AVR Volt. Max. (0-10.0)V
AVR Interface
38
Type
39
AVR Gain
40
AVR Stability
41
AVR Kd
42
PWM Gain
43
PWM Stability
44
PWM Kd
Timer Setting
1
Start Delay
2
Stop Delay
3
Preheat Delay
4
Cranking Time
Crank
Rest
5
Time
Safety
On
6
Delay
9
Cooling Time
HGM7110DC Genset Controller
Parameters
Defaults
(0-10.0)V
2.0
(0-1)
0
(0-500%)
20
(0-2000%)
20
(0-2000)
0
(0-10.0)V
0
2.0
(0-1)
0
(0-500%)
20
(0-2000%)
20
(0-2000)
0
(0-100%)
20
(0-100%)
20
(0-100)
0
(0-3600)s
1
(0-3600)s
1
(0-3600)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
10
Version: 1.0
HGM7110DC Genset Controller
Description
GOV output maximum voltage
0: Normal Output;1:Reversed Output
GOV Control
GOV Control
GOV Control
AVR output minimum voltage
AVR output maximum voltage
0: Normal Output;1:Reversed Output
AVR Control
AVR Control
AVR Control
PWM Control
PWM Control
PWM Control
Time from accumulator voltage has
fallen below the "Charge Start Voltage"
or remote start signal is active to start
genset.
Time from accumulator charging is
finished or remote start signal is
inactive to stop genset.
Time of pre-powering heat plug before
starter is powered up.
Time of starter power on
The waiting time before second power
up when engine start fail.
Alarms for low oil pressure, high
temperature,
under
frequency /voltage, charge fail are
inactive.
Radiating time before genset stop,
after it unloads.
2014-09-27
speed,
under
Page 34 of 68

Advertisement

Table of Contents
loading

Table of Contents