14.11
It is suitable for S6 engine control module. Engine type is DC9, DC12, and DC16.
Terminals of controller
Fuel relay output
Start relay output
CAN GND
CAN(H)
CAN(L)
Engine type: Scania
14.12
Suitable engine control mode is TAD1240, TAD1241, and TAD1242.
Terminals of controller
Fuel relay output
Start relay output
Auxiliary output 1
Terminals of controller
CAN GND
CAN(H)
CAN(L)
Engine type: Volvo
NOTE: When this engine type is selected, preheating time should be set to at least 3
seconds.
HGM7110DC Genset Controller

SCANIA

B1 connector
3
-
-
9
10

VOLVO EDC3

"Stand alone" connector
H
E
P
"Data bus" connector
-
1
2
Version: 1.0
HGM7110DC Genset Controller
Remark
Connect to starter coil directly
CAN
communication
line(connect with controller's terminal
only)
Impedance 120Ω connecting line is
recommended.
Impedance 120Ω connecting line is
recommended.
Remark
ECU power
Set Auxiliary output 1 as "ECU
power"
Remark
CAN
communication
line(connect with controller's terminal
only)
Impedance 120Ω connecting line is
recommended.
Impedance 120Ω connecting line is
recommended.
2014-09-27
shielding
shielding