9 SENSORS SETTING

1) When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if default temperature sensor is SGX (120° C resistor type), its sensor curve is SGX
(120° C resistor type); if select the SGD (120° C resistor type), the temperature sensor curve is
SGD curve.
2) When there is difference between standard sensor curves and using one, user can adjust
it in "curve type".
3) When input the sensor curve, X value (resistor) must be input from small to large,
otherwise, mistake occurs.
4) If select sensor type as "None", sensor curve is not working.
5) If corresponding sensor has alarm switch only, user must set this sensor as "None",
otherwise, shutdown or warning alarm occurs.