Smartgen HGM7110DC User Manual page 33

Dc genset controller
Table of Contents

Advertisement

No.
Items
21
Float Voltage
Nominal
22
Voltage
23
Charge OC
Charge
24
increment
Charge
Rest
25
Time
Charge
Limit
26
Time
27
System Mode
Two
28
Accumulators
Transfer Mode
29
Control Mode
30
GOV Volt. Min. (0-10.0)V
HGM7110DC Genset Controller
Parameters
Defaults
(0-1000) %
80
(0-1000) %
100
(0-1)
0
(0-200)%
120
(0-3)
0
(0-3600)s
10
(0-10) A
1
(0-1)
0
(0-300)h
30
(0-1)
0
(0-3)
0
(0-300)h
1
(0-2)
0
(0-1)
0
(0-2)
0
0
Version: 1.0
HGM7110DC Genset Controller
Description
Mode". If the genset enters into the
"Constant
Voltage
accumulator charges the genset with
its set value as soon as the charge
current has fallen below the set value.
The charging is finished if the charging
voltage has reached the "Charge Stop
Voltage".
Reserved
It's the load voltage if the "Gen
Priority" is selected.
0: Disable;
1: Enable
Charging Over Current Percentage
0: Warn; 1: Shutdown;
2: Trip and Stop; 3: Trip
Charging Over Current Delay
Adjust the charge increment manually
in Manual mode.
0: Enable;
1: Disable
In Auto mode, it is the waiting time
before second charging.
0: Enable;
1: Disable
0: Warn; 1: Shutdown;
2: Trip and Stop; 3: Trip
After the module is start successfully,
if the charging is not finished after the
set delay has expired, "Charge Limit
Time" alarm will be initiatd.
0: Accumulator Priority
1: Gen Priority
2: Double Accumulator Priority
0: Gap Power Supply
1:Uninterrupted Power Supply
0:GOV;
1:PWM;
2:AVR
GOV output minimum voltage
2014-09-27
mode",
the
Page 33 of 68