Power Ratings And Dimensions; Iec Ratings - Danfoss VACON 1000 Operating Manual

Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000
Operating Guide
Chemical environment condi-
tions
Environment corrosion cate-
gory
Electromagnetic compatibili-
ty environment
Seismic zone/Ground acceler-
ation
System burn-in at factory be-
fore delivery
ATEX area: Flammable prod-
uct/Zone
Noise level
Dimension and weight
Structure
Cabinet sheet metal thickness
Cable entry
Cooling system
Type
External auxiliary AC voltage
for cooling fans (optional,
+QDEX)
Protection level
IEC
UL
Auxiliaries
Cabinet lights
Power cell bypass
UPS for control voltage (DC)

11.2 Power Ratings and Dimensions

11.2.1 IEC Ratings

Danfoss A/S © 2021.06
>2000 m (on request)
IEC 60721-3-3: Class 3C2
According to ISO/EN 12944-2: C1 as default; C4 as an engineered op-
tion
IEC 61000-2-5: Industrial
Zone 2 (standard)
Zone 4 (optional, +SZ04)
4 h minimum, according to IEEE 1566
IEC 60079-10-1/2: as an engineered option, certified per EN
50495:2010
≤85 dB(A) at 1 m from the enclosure
See
11.2 Power Ratings and
Dimensions.
Doors and panels: 1.5 mm
Base: 5 mm
Input, motor, and control cables: Bottom and top
Forced air cooling including fan monitoring.
Fan redundancy available as option, +QDFR.
380–460 V AC, 50 Hz
380–460 V AC, 60 Hz
IP31 (standard)
IP42 (optional, +IP42)
NEMA 1
In the control cabinet
Automatic via IGBT, 1 ms bypass time (optional, +PPCB)
30 min running time
Specifications
AQ363633621020en-000201 / 172F3117 | 111

Advertisement