Danfoss Vacon NXP Applications Manual

Danfoss Vacon NXP Applications Manual

Grid converter. ac drives
Hide thumbs Also See for Vacon NXP:
Table of Contents

Advertisement

vacon nxp
®
ac drives
grid converter
application manual
arfiff03

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss Vacon NXP

  • Page 1 ® ac drives grid converter application manual arfiff03...
  • Page 3: Table Of Contents

    General vacon · 1 Table of contents Document: DPD01599B Software code: ARFIFF03V101 Version release date: 6.4.2016 General ..........................5 AFE Control ..........................5 Island (Static Power Supply) ....................5 Micro Grid ..........................6 1.3.1 Operation principle: Droop Speed Control Mode............7 1.3.2 Operation principle: Isochronous Speed Control Mode ...........
  • Page 4 2 · vacon General Parameter list ........................36 Basic parameters ......................... 36 Reference handling ....................... 36 4.2.1 DC Reference ......................37 4.2.2 Power / Frequency reference .................. 37 4.2.3 Reference adjust ....................... 37 4.2.4 AC voltage reference ....................37 Ramp control ........................38 Input signals ..........................
  • Page 5 General vacon · 3 4.14.1 Value control ......................54 4.14.2 DIN ID control 1 ......................54 4.14.3 DIN ID control 2 ......................54 4.14.4 DIN ID control 3 ......................55 4.14.5 DIN ID control 4 ......................55 4.15 Auto reset ..........................55 4.16 Grid voltage PI ........................
  • Page 6 4 · vacon General 5.9.9 Over Load Protection ....................102 5.10 Fieldbus ..........................103 5.11 Micro Grid ..........................105 5.12 Synch to external grid ......................108 5.13 Synch to shaft generator grid ..................... 109 5.14 ID functions ......................... 110 5.14.1 Value control ......................110 5.14.2 DIN ID control ......................
  • Page 7: General

    General vacon · 5 1. General This application is not kept backwards compatible. See chapter Compatibility issues before you update the application. The Grid Converter application is used to make AC grids with a possibility to operate in parallel with other power sources. The Grid Converter application has 3 different operation modes: Standard AFE mode.
  • Page 8: Micro Grid

    6 · vacon General Micro Grid Micro Grid mode controls the grid voltage and frequency. It functions like an ordinary generator. Micro Grid mode does not control DC Voltage. With the help of voltage droop and frequency droop, more than one Micro Grid and/or Generators can work together.
  • Page 9: Operation Principle: Droop Speed Control Mode

    General vacon · 7 1.3.1 Operation principle: Droop Speed Control Mode When the power demand increases, all generators on the grid allow frequency to droop. This will balance the load between all the generators on the grid. Then the power management system gives all generators a command to increase frequency so that the grid frequency is maintained at its nominal value.
  • Page 10: Shaft Generator

    8 · vacon General Shaft Generator The shaft generator is a system where the generator is connected to the main engine shaft that also runs the main propulsion. The disadvantage is that the main engine must run at nominal speed even if full power to the propeller is not necessary.
  • Page 11: Commissioning

    General vacon · 9 Commissioning NOTE! Before you start the commissioning, read the safety instructions in the user manual of your product. To use the Island, Micro Grid, or Shaft generator operation, you need a licence key. The AFE mode is available without a licence.
  • Page 12 10 · vacon General Figure 6. Connection Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205...
  • Page 13: Charting Of Dc

    General vacon · 11 Charting of DC This AFE application has its own charging control, P2.5.1.13 DC Charge (24 Vdc required for control board) and charging protection in case the external charging cannot get DC voltage to required level within set time P2.9.1.6 Charge Max Time (provided that the DC Voltage reaches the under voltage fault level).
  • Page 14: Start Sequence

    12 · vacon General NOTE! UPS may be needed during short circuit situation to keep MCB closed if control voltage is taken from the grid where the short circuit occurs. Start Sequence Start Ready to switch Fault Charge Reset DC-Link DC-Link >...
  • Page 15: Stop Sequence

    General vacon · 13 Stop sequence Modulating MCB Closed F64 A4 F64 A2 Stop Request MCB Closed (If DC > 85 %) (Delayed) Open MCB Stop Modulation (If Run State) Open MCB F64 A3 MCB Closed (Delayed) Figure 8. Stop sequence 1.10 Voltage compensation Grid Converter system will have voltage losses.
  • Page 16: Opt-D7

    14 · vacon General Filter Filter U4 = Transf. GC Side U5 = Transf. Grid Side Figure 9. Voltage compensation The normal operation voltage range in a land-based grid is usually between 80% and 115% of the grid nominal voltage. The voltage losses compensation is handled separately for Active power (kW) and Reactive power (kVar), the latter being more significant.
  • Page 17 General vacon · 15 To enable a zero power connection to an existing grid. To help in the commissioning of drive active power and reactive power voltage losses compensation when the actual grid voltage is visible in NCDrive. The OPT-D7 board is delivered with the transformer which is suitable for a voltage range up to 690 Vac.
  • Page 18: Licences

    Air and liquid-cooled drives that are compatible with AFE-II application ARFIFF05 or Grid Converter application ARFIFF03 are the only ones that are supported. See details in the GTC Product compatibility note, or for Air Cooled: Vacon NX AFE User Manual, and for Liquid Cooled: Vacon NXP Liquid Cooled Drives User Manual.
  • Page 19: Grid Converter Units

    See full details from AFE unit user manual. Air Cooled: Vacon NX AFE User Manual Liquid Cooled: Vacon NXP Liquid Cooled Drives User Manual. Air and liquid-cooled products listed in this chapter are compatible with Grid Converter application ARFIFF03. Hardware and software support for AFE use is only available for these products.
  • Page 20: Air Cooled 500 Vac Units, 465-800 Vdc

    18 · vacon General 1.14.1 Air cooled 500 Vac Units, 465-800 Vdc Code + MASG Frame IL-cont [A] IH-cont [A] Is [A] (2 s) NXA_0261 5 A0T02SG 1xFI9 NXA_0460 5 A0T02SG 1xFI10 NXA_1300 5 A0T02SG 1xFI13 1300 1150 2070 1.14.2 Air Cooled 690 Vac Units, 640-1100 Vdc Code + MASG Frame...
  • Page 21: Control I/O

    Control I/O vacon · 19 2. Control I/O Table 1. Minimum recommended I/O configuration. OPT-A1 Terminal Signal Description +10V Reference voltage output Voltage for potentiometer, etc. AI1+ Analogue input 1. Input range selected by jumpers. Range 0-10V, R = 200Ω Default range: Voltage 0 –...
  • Page 22: Monitoring Signals

    20 · vacon Monitoring signals 3. Monitoring signals The menu M1 (Monitoring) has all the monitoring values. Values are only for monitoring, and cannot be altered on the control panel. Monitoring value tables 3.1.1 Monitoring values 1 (Control panel: menu M1.1) Code Parameter Unit...
  • Page 23: Fieldbus Monitoring Values (Control Panel: Menu M1.3)

    Monitoring signals vacon · 21 Reference V1.2.12 Grid State 1882 V1.2.13 Mindex 1858 Modulation Index 3.1.3 Fieldbus monitoring values (Control panel: menu M1.3) Code Parameter Unit Description V1.3.1 FB Control Word 1160 Control word from fieldbus V1.3.2 FB Status Word Status word to fieldbus V1.3.3 Fault Word 1...
  • Page 24: Description Of Monitoring Values

    22 · vacon Monitoring signals Description of monitoring values 3.2.1 Monitoring 1 values V1.1.1 DC-Link Voltage V ID1108 The measured DC voltage, filtered. V1.1.2 DC Voltage Ref. % ID1200 The DC voltage reference. Compared to given supply voltage. DC Voltage = Grid Nom Voltage (P2.1.1) * 1.35 * DC Voltage Ref. 1025 Vdc 690 Vac ∗...
  • Page 25 Monitoring signals vacon · 23 V1.1.9 Status Word (Application) ID 43 The Application Status Word combines different statuses of the drive to one data word. Status Word (Application) ID43 FALSE TRUE Not in Ready state Ready Not Running Running No Fault Fault Quick stop active Quick stop not active...
  • Page 26: Monitoring 2 Values

    24 · vacon Monitoring signals V1.1.14 AC Voltage Reference V ID1556 The used AC voltage reference. V1.1.15 DC Voltage Max Limit ID1606 The drive will limit the DC reference to inside drive specification, but allows higher reference if lower supply voltage. This shows the final limit of the DC reference. 3.2.2 Monitoring 2 values V1.2.1...
  • Page 27 Monitoring signals vacon · 25 V1.2.7 Frequency Reference ID1752 The used frequency reference. In AFE mode, the frequency reference is determined internally when the synchronisation is made. In Island and Micro Grid mode, the reference is used for a static power supply, and a power drooping in Micro Grid mode. V1.2.8 Current A ID 1113...
  • Page 28: Fieldbus Monitoring Values

    26 · vacon Monitoring signals 3.2.3 Fieldbus monitoring values V1.3.1 FB Control Word ID 1160 The control word from fieldbus. The table below is for “2 / Vacon AFE 1” Selection (P2.10.19) in bypass operation for such fieldbus board that natively supports this or can be parameterised to bypass mode.
  • Page 29 Monitoring signals vacon · 27 V1.3.2 FB Status Word ID 68 This is referred as GeneralStatusWord in the fieldbus manual. See details in the fieldbus manual. FB Status Word ID68 Signal Comment 0 = Drive not ready to charge Ready On 1 = Drive ready to charge 0 = Drive not ready to run Ready Run...
  • Page 30 28 · vacon Monitoring signals V1.3.3 Fault Word 1 ID 1172 FALSE TRUE F1 Over current, F31 IGBT, F41 IGBT F2 Over Voltage F9 Under Voltage F91 Short Circuit F3 Earth Fault F14 Unit Over temperature Temperature fault from measurements F56 PT100, F29 Thermistor F10 Line Synch Fault F52 Keypad or OC communication fault F53 Fieldbus fault...
  • Page 31 Monitoring signals vacon · 29 V1.3.5 Warning Word 1 ID 1174 Warning Comment W91 Short Circuit Triggered when current has reached current limit W29 Thermistor Not implemented F53_FB_Warning_Slot_D F67_FB_Warning_Slot_E W14 Unit Temperature V1.3.6 FB Micro Grid CW1 ID 1700 Control for the Micro Grid operations. FB Micro Grid CW1 ID1700 Signal Comment...
  • Page 32 30 · vacon Monitoring signals V1.3.7 FB Micro Grid SW1 ID 1701 Status of the Micro Grid operations. Micro Grid Status Word Signal Comment Charge Control active Charging Internal Charging switch status MCB control MCB status Run Enabled Drive Ready AFE mode active Island mode active Micro Grid mode active...
  • Page 33 Monitoring signals vacon · 31 V1.3.10 MC Status ID 64 For the fieldbuses that do not have their own state machine, this value is sent to fieldbus. Motor Control Status Word FALSE TRUE Not in Ready state Ready Not Running Running Direction Clockwise Counter clockwise...
  • Page 34: I/O Monitoring Values

    32 · vacon Monitoring signals 3.2.4 I/O monitoring values V1.4.1 DIN1, DIN2, DIN3 ID 15 V1.4.2 DIN4, DIN5, DIN6 ID 16 DIN1/DIN2/DIN3 status DIN4/DIN5/DIN6 status DIN3 DIN6 DIN2 DIN5 DIN1 DIN4 V1.4.3 DIN Status 1 ID 56 V1.4.4 DIN Status 2 ID 57 DIN StatusWord 1 DIN StatusWord 2...
  • Page 35: Master Follower Monitoring Values

    Monitoring signals vacon · 33 V1.4.12 PT100 Temp. 1 °C ID 50 V1.4.13 PT100 Temp. 2 °C ID 51 V1.4.14 PT100 Temp. 3 °C ID 52 V1.4.15 PT100 Temp. 4 °C ID 69 V1.4.16 PT100 Temp. 5 °C ID 70 V1.4.17 PT100 Temp.
  • Page 36: Activation Status

    34 · vacon Monitoring signals V1.5.2 Drive 1 Status Word ID1801 V1.5.3 Drive 2 Status Word ID1802 Follower Drive status word FALSE TRUE Not in Ready state Ready Not Running Running No Fault Fault ChargeSwState Run Disabled Run Enable No Warning Warning No Run Request Run Request...
  • Page 37 Monitoring signals vacon · 35 V1.7.2 Licence Status ID1996 This value indicates the status of the licence key activation. 0 / No Function If PLC receives this number from this ID, it is likely that the Micro Grid application is not loaded on the drive.
  • Page 38: Parameter List

    36 · vacon Parameter list 4. Parameter list In this chapter you will find the lists of parameters that are available in this application. Basic parameters Table 2. Basic parameters , G2.1 Code Parameter Unit Default Description AFE: AFE: Set the nominal voltage of the 500V: 500V: grid.
  • Page 39: Dc Reference

    Parameter list vacon · 37 4.2.1 DC Reference Table 4. Code Parameter Unit Default Description P2.2.3.1 DC Voltage Drooping AFE drooping DC-voltage. DC Voltage Reference P2.2.3.2 10000 1000 1199 Ramp Rate P2.2.3.3 DC Voltage Reference 15.00 0.00 1760 Filtering time P2.2.3.4 DC Reference Offset 0,00...
  • Page 40: Ramp Control

    38 · vacon Parameter list Ramp control Table 8. Code Parameter Unit Default Description P2.3.1 Ramp Time 3200.0 25.0 2.00 Hz/s if Range 50 Hz P2.3.2 Ramp Range 0.01 100.00 50.00 1980 Input signals 4.4.1 Basic settings Table 9. Code Parameter Unit Default...
  • Page 41: Digital Inputs

    Parameter list vacon · 39 4.4.2 Digital inputs Table 10. Digital inputs , G2.2.1 Code Parameter Unit Default Description P2.4.2.1 Start Signal 1 E.10 P2.4.2.2 Start Signal 2 E.10 P2.4.2.3 Open MCB E.10 1600 Forced open command P2.4.2.4 CB Feed Back E.10 1453 AFE MCB feedback (MCB 1)
  • Page 42: Analogue Input 1

    40 · vacon Parameter list 4.4.3 Analogue input 1 Table 11. Analogue Input 1, G2.2.2 Code Parameter Unit Default Description P2.4.3.1 AI1 signal selection E.10 P2.4.3.2 AI1 filter time 0.000 32.000 0.000 AI1 custom P2.4.3.3 -160.00 160.00 0.00 minimum setting AI1 custom P2.4.3.4 -160.00...
  • Page 43: Analogue Input 4

    Parameter list vacon · 41 4.4.6 Analogue input 4 Table 14. Analogue Input 2, G2.2.3 Code Parameter Unit Default Description P2.4.6.1 AI4 signal selection E.10 P2.4.6.2 AI4 filter time 0.000 32.000 0.000 AI4 custom P2.4.6.3 -160.00 160.00 0.00 minimum setting AI4 custom P2.4.6.4 -160.00...
  • Page 44: Delayed Do 1

    42 · vacon Parameter list 4.5.2 Delayed DO 1 Table 16. Delayed DO 1, G2.3.2 Code Parameter Unit Default Description Connect the delayed DO1 signal to the digital output of P2.5.2.1 Dig.Out 1 Signal E.10 your choice with this parameter. 0 = Not used 1 = Ready 2 = Run...
  • Page 45: Analogue Output 1

    Parameter list vacon · 43 4.5.4 Analogue output 1 Table 18. Analogue output signals, G2.3.4 Code Parameter Unit Default Description Connect the AO1 signal to P2.5.4.1 Iout 1 signal AnOUT:0.1 AnOUT:E.10 AnOUT:A.1 the analogue output of your choice with this parameter. 0 =Not used 1 = DC Voltage 2 = Drive Current...
  • Page 46: Analogue Output 2

    44 · vacon Parameter list 4.5.5 Analogue output 2 Table 19. Analogue output signals, G2.3.4 Code Parameter Unit Default Description Connect the AO1 signal to P2.5.5.1 Iout 2 signal AnOUT:0.1 AnOUT:E.10 AnOUT:A.1 the analogue output of your choice with this parameter. 0 = Not used 1 = DC Voltage 2 = Drive Current...
  • Page 47: Analogue Output 3

    Parameter list vacon · 45 4.5.6 Analogue output 3 Table 20. Analogue output signals, G2.3.4 Code Parameter Unit Default Description Connect the AO1 signal to P2.5.6.1 Iout 3 signal AnOUT:0.1 AnOUT:E.10 AnOUT:A.1 the analogue output of your choice with this parameter. 0 = Not used 1 = DC Voltage 2 = Drive Current...
  • Page 48: Limit Settings

    46 · vacon Parameter list Limit settings 4.6.1 Current limit Table 22. Code Parameter Unit Default Description P2.6.1.1 Current Limit Varies Varies Total current limit P2.6.1.2 Short Circuit Level 800,1 800.0 1620 Disabled above 499.0% P2.6.1.3 Short Circuit Time 5000 1515 High Freq.
  • Page 49: Dc Voltage

    Parameter list vacon · 47 4.6.5 DC voltage Table 26. Code Parameter Unit Default Description P2.6.5.1 Under Voltage Limit 0.00 320.00 65.00 1524 P2.6.5.2 Over voltage limit 0.00 320.00 120.00 1523 Drive control Table 27. Drive control, G2.6 Code Parameter Unit Default Description...
  • Page 50: Protections

    48 · vacon Parameter list Protections 4.9.1 General Table 29. Protections, G2.9 Code Parameter Default Description 0 = No response 1 = Warning Thermistor Fault P2.9.1.1 2 / Fault 2 = Fault, stop acc. stop Response mode 3 = Fault, stop by coasting Overtemperature P2.9.1.2 2 / Fault...
  • Page 51: Earth Fault

    Parameter list vacon · 49 4.9.3 Earth fault Table 31. Code Parameter Unit Default Description P2.9.3.1 Earth Fault Response 2 / Fault 1756 P2.9.3.2 Earth Fault Level 1333 4.9.4 Fieldbus fault Table 32. Code Parameter Unit Default Description FB Fault response P2.9.4.1 Slot D FB Fault response...
  • Page 52: Voltage

    50 · vacon Parameter list 4.9.8 Voltage Table 36. Code Parameter Unit Default Description Voltage Supply P2.6.8.1 1629 Response Voltage Low Trip P2.6.8.2 0.00 320.00 75.00 1891 Limit Voltage Low P2.6.8.3 0.00 320.00 90.00 1880 Warning Limit Voltage High Trip P2.6.8.5 0.00 320.00...
  • Page 53: Fieldbus

    Parameter list vacon · 51 4.10 Fieldbus Table 39. Fieldbus, G2.10 Code Parameter Unit Default Description FB Actual Value P2.10.1 10000 1853 P2.10.2 FB Data Out1 Sel 10000 1104 P2.10.3 FB Data Out2 Sel 10000 1508 P2.10.4 FB Data Out3 Sel 10000 1172 P2.10.5...
  • Page 54: Micro Grid

    52 · vacon Parameter list 4.11 Micro Grid Table 40. Micro Grid, G2.7 Code Parameter Unit Default Description 0 = AFE 1 = Island 2 = Micro Grid 3 = Island-AFE P2.11.1 Control Mode 0 / AFE 1531 4 = Island-Micro Grid 5 = Island-Micro Grid (Reserved) 6 = FreeSelect...
  • Page 55: Synchronisation To External Grid

    Parameter list vacon · 53 4.12 Synchronisation to external grid Table 41. Code Parameter Unit Default Description Used to compensate for transformer angle offset. P2.12.1 Synch. Offset -3172 3171 1601 (3172 equals 180 degrees offset). Gives synchronisation point P2.12.2 Synch Reference -3170 3170 1611...
  • Page 56: Id Control Functions

    54 · vacon Parameter list 4.14 ID control functions 4.14.1 Value control Table 43. Power reference input signal selection, G2.2.8 Code Parameter Unit Default Cust Description Control Input Signal P2.14.1.1 10000 1580 Control Input Off P2.14.1.2 -32000 32000 1581 Limit Control Input On P2.14.1.3 -32000...
  • Page 57: Din Id Control 3

    Parameter list vacon · 55 4.14.4 DIN ID control 3 Table 46. DIN ID control parameters, G2.2.8 Code Parameter Unit Default Cust Description Slot Board input No. P2.14.4.1 ID Control DIN E.10 1578 If 0.1 ID61 can be controlled from FB Select ID that is P2.14.4.2 Controlled ID...
  • Page 58: Keypad Control (Control Panel: Menu M3)

    56 · vacon Parameter list 4.17 Keypad control (Control panel: menu M3) Table 50. Keypad control parameters M3 Code Parameter Default Unit Description 0 = PC Control 1 = I/O terminal P3.1 Control Place 1403 2 = Keypad (Default) 3 = Fieldbus 4 = SystemBus P3.2 Licence Key...
  • Page 59: Description Of Parameters

    Description of parameters vacon · 57 5. Description of parameters Basic parameters 2.1.1 Grid Nominal Voltage ID110 This parameter sets the incoming line voltage for the regenerative drive. Set this parameter to the nominal line voltage at the installation site. Used also as a reference point for grid voltage protection functions.
  • Page 60 58 · vacon Description of parameters For testing purposes (FAT) feeding transformer should not be less than 20% of the unit nominal current or following breakers or fuses. 2.1.4 System Rated Cos Phi ID120 Enter the system rated Cos Phi. 2.1.5 System Rated kVA ID213...
  • Page 61: Transformer Parameters

    Description of parameters vacon · 59 5.1.1 Transformer parameters These parameters are used to scale voltage so that the parameter P2.1.1 Grid Nominal Voltage can be given a value as actual grid voltage. The drive will calculate the actual drive terminal voltage based on these values.
  • Page 62: Reference Handling

    60 · vacon Description of parameters Reference handling 2.2.1 DC Voltage Reference ID1462 This parameter sets the DC Voltage reference in % of the Nominal DC voltage. If P2.1.5 System Nominal DC is zero then Nominal DC voltage = 1.35 * Grid Nom. Voltage (P2.1.1). Final DC Voltage Ref (V1.1.2) = Nominal DC Voltage * DC Voltage Reference The DC Voltage will be maintained at this level when the regenerative unit is running.
  • Page 63 Description of parameters vacon · 61 For example, if drooping is 3.00% and active current is 50%, the DC voltage reference is reduced by 1.5%. With drooping, paralleled units can be balanced by adjusting the DCVoltReference to slightly different values. Voltage Actual Reference...
  • Page 64: Power /Frequency Reference

    62 · vacon Description of parameters 12000 10000 Unfiltered 8000 1 s filter time 6000 4000 63 % 2000 FreqRef 2nd order Figure 14. 2.2.3.4 DC Reference Offset Offset for DC Reference, used to balance parallel unit active current while using same DC Reference P2.2.1.
  • Page 65 Description of parameters vacon · 63 if 100% of Base Current Reference is given, the drive will feed 100% power to the grid. The situation is the same with the frequency reference set to 52 Hz and with 2.000 Hz drooping.
  • Page 66: Reference Adjust Functions

    64 · vacon Description of parameters 0 = No action. 1 = Reference set to P2.2.6.4 when at STOP state. 2 = Reference set to P2.2.6.4 when AFE mode is active. 3 = Reference set to P2.2.6.4 when AFE mode is active or drive in STOP state. 2.2.4.9 Base Reference at Stop State ID1538 Base reference on situation selected by P2.2.6.7 Base Reference to Zero.
  • Page 67 Description of parameters vacon · 65 NOTE! Some cases when inductor size and losses are compensated, the zero load voltage may need to decrease. P2.2.6.4 Capacitor Size (ID1460) AFE: This parameter defines the reactive current going to the LCL filter capacitor. It compensates the LCL effect to the reactive current by adjusting the reactive current reference internally.
  • Page 68: Ramp Control

    66 · vacon Description of parameters Together with inductor size and inductor losses voltage will be increased 18 Vac + 4,5 Vac = 22,5 Vac from Supply Voltage parameter -> 422,5 Vac. 2.2.6.7 Voltage Down (DigIn) ID1551 Select a digital input to decrease the supply voltage with a set ramp rate. 2.2.6.8 Voltage Up (DigIn) ID1550...
  • Page 69: Input Signals

    Description of parameters vacon · 67 Input signals 5.4.1 Basic settings P2.4.1.1 Start/Stop Logic Selection ID300 Start/Stop Logic This parameter defines the start/stop logic when using I/O control. 0 Start – No Act – Start Drive – No Action Start 1: closed contact = start command DI “Start 1” 1 StartP-StopP –...
  • Page 70: Digital Input Signals

    68 · vacon Description of parameters 5.4.2 Digital input signals 2.4.2.1 Start Signal 1 ID403 Signal selection 1 for the start/stop logic. This parameter is used to select the input for Run Request signal 2.4.2.2 Start Signal 2 ID404 Signal selection 1 for the start/stop logic. This parameter is used to select the input for Stop Request signal.
  • Page 71 Description of parameters vacon · 69 2.4.2.9 Synchronisation ID1602 This input is used to the synchronisation of the external network when the drive is already generating network but in a different phase. It can be used only when OPT-D7 board is installed and measurements are on the external network side. When the input is activated, the drive uses line frequency as a frequency reference and adjusts the voltage angle to correspond with the line voltage angle with given hysteresis.
  • Page 72 70 · vacon Description of parameters 2.4.2.14 Grid Close Enabled ID1705 An interlock for the NET contactor (shore). If the interlock is not used in the system, the option = FALSE must be selected. 2.4.2.15 Use MCB 2 Control ID1708 This parameter is useful if 2 different supply networks are used.
  • Page 73 Description of parameters vacon · 71 5.4.2.1 Forced control place The digital inputs can be used to bypass parameter P3.1 Control Place, for example, in an emergency situation when PLC is not able to send command to the drive. Figure 19. Control place selection priority order P2.4.2.23 Control from I/O terminal ID409 “I/O Term Control”...
  • Page 74: Analogue Inputs 1-4

    72 · vacon Description of parameters 5.4.3 Analogue inputs 1-4 2.4.3.1 AI1 signal selection ID377 “AI1 Signal Sel” 2.4.4.1 AI2 signal selection ID388 “AI2 Signal Sel” 2.4.5.1 AI3 signal selection ID141 “AI3 Signal Sel” 2.4.6.1 AI4 signal selection ID152 “AI4 Signal Sel” Connect the AI3/AI4 signal to the analogue input of your choice with this parameter.
  • Page 75 Description of parameters vacon · 73 AI3/AI4 Output 100 % 40 % Analogue 80 % 100 % Custom Input Custom Figure 21. 2.4.3.5 AI1 signal inversion ID387 “AI1 Signal Inv” 2.4.4.5 AI2 signal inversion ID398 “AI2 Signal Inv” 2.4.5.5 AI3 signal inversion ID151 “AI3 Signal Inv”...
  • Page 76 74 · vacon Description of parameters 5.4.3.1 Analogue input to any parameter This function allows you to control any parameter by using an analogue input. Use a parameter to select the range of the control area and the ID number for the parameter that is controlled. 2.4.3.6 Analogue input 1, minimum value ID303 “AI1 Scale Min”...
  • Page 77: Output Signals

    Description of parameters vacon · 75 Output signals 5.5.1 Digital output signals 2.5.1.1 Main Circuit Breaker 1 Close Control ID1218 “MCB1 Close Cont” AFE contactor, fixed to the relay output B.2. When P2.5.1.2 is not activated, this output will stay high as long as MCB must be closed. When the signal goes low, MCB must be open.
  • Page 78 76 · vacon Description of parameters 2.5.1.13 Charge control When this is activated, the drive will start charging of DC from the start command and go directly to RUN state. The charging starts from the start command. 2.5.1.14 Common alarm Drive has a warning active.
  • Page 79: Delayed Digital Output 1 & 2

    Description of parameters vacon · 77 5.5.2 Delayed digital output 1 & 2 2.5.2.1 Dig.Out 1 Signal 2.5.3.1 Dig.Out 2 Signal Connect the delayed DO1 signal to the digital output of your choice with this parameter. 2.5.2.2 DO1 Content 2.5.3.2 DO2 Content 0 = Not used 1 = Ready...
  • Page 80: Analogue Output 1 & 2 & 3

    78 · vacon Description of parameters 2.5.2.5 ID.Bit Free DO 2.5.3.5 ID.Bit Free DO Select the signal for controlling the DO. The parameter must be set in the format xxxx.yy where xxxx is the ID number of a signal and yy is the bit number. For example, the value for DO control is 1174.02 .
  • Page 81 Description of parameters vacon · 79 2.5.4.3 Iout 1 Filter Time 2.5.5.3 Iout 2 Filter Time 2.5.6.3 Iout 3 Filter Time Defines the filtering time of the analogue output signal. Setting this parameter value 0 will deactivate the filtering. First order filtering is used for the analogue output signals. 12000 10000 8000...
  • Page 82 80 · vacon Description of parameters 2.5.4.5 Iout 1 Minimum 2.5.5.5 Iout 2 Minimum 2.5.6.5 Iout 3 Minimum 0 = Set minimum value to 0 mA (0%) 1 = Set minimum value to 4 mA (20%) 100 % Analogue Inverted Output 20 % Function...
  • Page 83: Options

    Description of parameters vacon · 81 2.5.4.7 Iout 1 Offset 2.5.5.7 Iout 2 Offset 2.5.6.7 Iout 3 Offset Add –100.0 to 100.0% to the analogue output. 100 % Scaling Analogue 200 % Output 50 % Scaling 50 % 20 % 50 % Function 100 %...
  • Page 84 82 · vacon Description of parameters P2.5.7.4 DC Supervision Limit ID1454 This parameter defines when FB Status Word B10 is high (ID68). The Bit is high when DC voltage is above the value set by this parameter. P2.5.7.5 CB Close Mode This parameter defines how the closing of circuit breaker is handled.
  • Page 85: Limit Settings

    Description of parameters vacon · 83 Limit settings 5.6.1 Current limits 2.6.1.1 Current Limit The parameter sets the current limit for the Grid Converter unit. Set the value to correspond to the maximum peak overload for the unit or if needed, to required short circuit current (I The maximum value for air cooled unit is I and liquid cooled unit I...
  • Page 86 84 · vacon Description of parameters Example Air Cooled AFE unit 460 A 500 Vac : System Rated Current: 385 A (I Current Limit: 693 A (I √ 2 1.25 319 % Short Circuit Level: Short Circuit detection Three phase Fault: F91 Short Circuit 4 * I Over Current Trip Limit ) * 1,77...
  • Page 87: Active Current Limits

    Description of parameters vacon · 85 2.6.1.5 BiPhase Fault Voltage Level. The BiPhase fault is detected by monitoring the supply voltage. Set this value lower than the supply voltage would be in normal operation. Short Circuit detection Two phase Fault: F91 Short Circuit Supply Voltage ShortCircuitTime BiPhsFaultVLevel...
  • Page 88: Frequency Limits

    86 · vacon Description of parameters 5.6.3 Frequency limits NOTE: This functionality is not Grid Code functionality even if functionality may be similar. 2.6.3.1 Line Low Frequency Trip Limit If the drive output frequency goes below this level, the drive will trip to a line synch fault. Use this limit as a final and immediate protection function for the grid or generator.
  • Page 89: Micro Grid Limits

    Description of parameters vacon · 87 5.6.4 Micro Grid limits 2.6.4.1 Current Limit Minimum An active current limit from AC to DC direction. This limit affects the Island and uGrid operation modes but not the AFE operation mode. 2.6.4.2 Current Limit Maximum An active current limit from DC to AC direction.
  • Page 90: Dc Voltage Regulators

    88 · vacon Description of parameters 2.6.4.5 Current Limit Ti The integration time for the current limit operation. 2.6.4.6 Current Limit Max Minimum This parameter defines the minimum limit for the maximum current limit. Use this function to limit minimum when PLC control value to zero. The value zero will cause instability in the control.
  • Page 91: Drive Control

    Description of parameters vacon · 89 Drive control 2.7.1 Switching Frequency The switching frequency of the IGBT Bridge in kHz. Changing the default value can have an impact on the LCL filter operation. 2.7.2 Regen Options 1 This packed bit word is made for enabling/disabling different control options for the regeneration control.
  • Page 92 90 · vacon Description of parameters 2.7.4 Start Delay This parameter defines a starting delay when a run command is given. When programming different delays to parallel units, the units will start in sequence. This is necessary in parallel units to make sure that the synchronisation does not happen simultaneously in all the drives.
  • Page 93 Description of parameters vacon · 91 2.7.6 Control Options 1 ID1707 B03 = +8 = Disable D7 frequency monitoring for diagnostic. Used for testing purposes. B04 = +16 = Disable D7 voltage monitoring for diagnostic. Used for testing purposes. B05 = +32 = Keep frequency drooping while synchronising to external grid. B06 = +64 = Enable external grid contactor closing in STOP state.
  • Page 94: Master Follower

    92 · vacon Description of parameters Master follower 5.8.1 Master follower mode 1 & 2 A system that has two back-to-back AFE units can be controlled by using system bus communication. This will reduce the need for I/O control, because you have to, for example, give a start command only on the drive.
  • Page 95 Description of parameters vacon · 93 2.8.1 MF Mode This parameter is used when you have two drives in Shaft Generator operation and the drives must operate to an upper system as a single unit. 0 = Single drive System bus is deactivated. For example, in Shaft Generator system both drives are controlled separately.
  • Page 96: Protections

    94 · vacon Description of parameters Protections 5.9.1 General settings 2.9.1.1 Thermistor Fault Response 0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting Setting the parameter to will deactivate the protection.
  • Page 97 Description of parameters vacon · 95 2.9.1.7 MCB at Fault Defines action for the main circuit breaker when the drive has a fault. F1 Over Current, F31 Hardware IGBT and F41 Software IGBT will open MCB immediately regardless of the setting of this parameter. 0 = Keep closed 1 = Open at any fault situation 2.9.1.8...
  • Page 98: Pt-100

    96 · vacon Description of parameters P2.9.1.14 Reactive Current Limit Response ID1981 This function can be used to generate a fault or a warning when the reactive current exceeds 110% value. 0 = No response 1 = Warning 2 = Fault 5.9.2 PT-100 The PT100 protection function is used to measure the temperature and give a warning and/or a fault...
  • Page 99: Earth Fault

    Description of parameters vacon · 97 2.9.2.5 Number of PT100 2 inputs in use ID743 “PT100 2 Numbers” If you have a two PT100 input boards installed in your AC drive, you can select the number of PT100 inputs in use on the second board. See also the Vacon I/O boards manual.
  • Page 100: External Fault

    98 · vacon Description of parameters 5.9.5 External fault 2.9.5.1 Response to External Fault 1 ID701 “External Fault 1” 2.9.5.2 Response to External Fault 2 ID1504 “External Fault 1” Defines response when a digital input signal is used to give signal about an external condition to which the drive needs to react.
  • Page 101: Grid Frequency

    Description of parameters vacon · 99 P2.9.6.2 Voltage Low Warning Limit ID1893 Low limit for a warning indication. A percentage value from a set supply voltage parameter. P2.9.6.3 Voltage Low Trip Limit ID1899 Low limit for a fault indication. A percentage value from a set supply voltage parameter. The common tripping limit of the land based grid code standard is 80 % of Un within 200 P2.9.6.4 Voltage High Warning Limit...
  • Page 102: Supply Voltage

    100 · vacon Description of parameters P2.9.7.1 Freq. Supply Response ID1627 0 = No response 1 = Warning 2 = Fault P2.9.7.2 Freq. D7 Response ID1628 0 = No response 1 = Warning 2 = Fault P2.9.7.3 Freq. Low Warning Limit ID1780 Low limit for a warning indication.
  • Page 103 Description of parameters vacon · 101 P2.9.8.2 Voltage Low Trip Limit ID1891 When the supply voltage drops below this limit, the drive will trip to an F70 Supply voltage fault. If the drive is already at the current limit, this low voltage trip limit is not active.
  • Page 104: Over Load Protection

    102 · vacon Description of parameters 5.9.9 Over Load Protection With this function it is possible to select if Current %, Active Current or Reactive Current is used for over load protection. Over Load is based on internal counter that is increased when input value is above 105 % level and decreased when below 105 % level.
  • Page 105: Fieldbus

    Description of parameters vacon · 103 2.9.9.4 Over Load Maximum Step ID1840 “OverLoadMaxStep” Step in the over load counter when the input value is at maximum input level defined by P2.9.9.3. 2.9.10 Fault Simulation ID1569 “Fault Simulation” With this parameter it is possible to simulate different faults without actually making, for example, an over current situation.
  • Page 106 104 · vacon Description of parameters 2.10.10 FB Data In 1 Sel 2.10.11 FB Data In 2 Sel 2.10.12 FB Data In 3 Sel 2.10.13 FB Data In 4 Sel 2.10.14 FB Data In 5 Sel 2.10.15 FB Data In 6 Sel 2.10.16 FB Data In 7 Sel 2.10.17...
  • Page 107: Micro Grid

    Description of parameters vacon · 105 2.10.23 SW ID.Bit selection B11 ID1907 2.10.24 SW ID.Bit selection B12 ID1908 2.10.25 SW ID.Bit selection B13 ID1909 2.10.26 SW ID.Bit selection B14 ID1910 Select the bit that used in FB Status Word Bit 11, 12, 13 and 14. 2.10.27 uGrid CW B12 parameter ID891 “uCW B12”...
  • Page 108 106 · vacon Description of parameters 2.11.2 Frequency Droop Drooping related to the active current in Hz. Set to the same value as all other power sources drooping. Used in uGrid operation mode. Freq. Change 52,0 Hz 51,5 Hz 51,0 Hz 50,5 Hz Related Load...
  • Page 109 Description of parameters vacon · 107 1 = Zero Power from Supply Frequency This selection is only possible with unit FI9 and bigger. The drive monitors the supply frequency by itself and uses this as a starting point for power drooping control. 2 = Drooping The drive does not control the power to zero but goes directly to the drooping control with set parameters.
  • Page 110: Synch To External Grid

    108 · vacon Description of parameters 5.11.1.2 AFE operation mode selection When using digital input P2.4.2.17 AFE Mode 2 and P2.4.2.18 AFE Mode 3 with the parameters below, it is possible to select the operation independently for both the digital inputs. AFE Mode 2 Used AFE Mode IN 0...
  • Page 111: Synch To Shaft Generator Grid

    Description of parameters vacon · 109 2.12.2 Synch Reference Use of P:Synch. Offset do not affect the error value that is shown in monitoring variable “D7 Synch. Error”. Therefore you must give the reference for synchronization; usually this reference is roughly the same as P:”Synch. Offset” value, depending on the system. (3072 equals 180 degrees offset).
  • Page 112: Id Functions

    110 · vacon Description of parameters P2.13.3 Synch Gain 1778 The phase synchronisation gain. The frequency reference at 180 degree difference. P2.13.4 Phase Synch Ramp Time 1777 The ramp time for the synchronisation function. When the synchronisation mode is after the ramp, this time is active all the time.
  • Page 113 Description of parameters vacon · 111 P2.14.1.6 Control Output Signal ID ID1585 “ContrlOutSignID” This parameter defines which parameter is forced to On and Off values when selected input signal exceeds the set limits. P2.14.1.7 Control Mode ID1586 “Control Mode” This parameter defines how the value control output behaves. 0 = SR ABS Absolute input value is used to make a step change in the output between On and Off values.
  • Page 114: Din Id Control

    112 · vacon Description of parameters Control Value Control value Negative Positive value value value value Figure 46. 3 = SR Input value is used to make a step change in the output between On and Off values. 4 = Scale ABS Input values is scaled linearly between On and Off values.
  • Page 115: Grid Voltage Pi Controller

    Description of parameters vacon · 113 P2.14.4.2 DIN Controlled ID ID15719 “Controlled ID” Select a parameter ID controlled by ID1570. P2.14.2.3 Value for Low digital input (FALSE) ID1572 “FALSE Value” P2.14.3.3 Value for Low digital input (FALSE) ID1592 “FALSE Value” P2.14.4.3 Value for Low digital input (FALSE) ID15794 “FALSE Value”...
  • Page 116: Grid Voltage Pi Opt-D7 Limits

    114 · vacon Description of parameters P2.15.4 PI Max Adjust ID360 This parameter defines maximum adjustment that PI controller can made to voltage. 5.15.1 Grid voltage PI OPT-D7 limits These parameters define the limits within which the OPT-D7 measurements must remain in order for the PI controller to remain active.
  • Page 117: Keypad Control Parameters

    Keypad control parameters vacon · 115 6. Keypad control parameters Unlike the parameters listed above, these parameters are located in the M3 menu of the control panel. The reference parameters do not have an ID number. P3.1 Control Place ID125 “Control Place”...
  • Page 118: Fb Status And Control In Detail

    116 · vacon FB Status and control in detail 7. FB Status and control in detail P2.10.19 State machine This mode makes fieldbus control operate as is explained in the 1 / Basic fieldbus board manual. Simple control word that is used in modes where the control word from fieldbus is used as such.
  • Page 119: State Machine: Standard

    FB Status and control in detail vacon · 117 B02: FALSE = No Action, TRUE = Fault Reset Fault Reset: Resets active faults. State Machine: Standard 7.3.1 Control Word: Standard Table 52. FB Control Word Standard FALSE TRUE Comment Open CB Charge DC Stop Request Run Request...
  • Page 120: State Machine: Vacon Afe 1

    118 · vacon FB Status and control in detail State machine: Vacon AFE 1 7.4.1 Control Word: Vacon AFE 1 FB Control Word Vacon AFE 1 Comment FALSE TRUE Open CB Charge DC Stop Request Run Request Use this for start and stop command No Action Fault Reset 0 >...
  • Page 121: Fb Status Word

    FB Status and control in detail vacon · 119 FB Status Word FB Status Word ID68 Comment FALSE TRUE Drive own DC charge function disabled if FALSE DC Charge Disabled Ready to DC Charge DC Charged and main CB closed. Not ready to operate Ready to operate Drive in Run state...
  • Page 122 120 · vacon FB Status and control in detail B06: FALSE = CB Control OK, TRUE = CB Control Not OK CB Control OK: CB control and the drive internal status are the same. CB Control Not OK: The drive internal status to close the circuit breaker is high but the application logic requests for the circuit breaker to open.
  • Page 123: Problem Solving

    Problem solving vacon · 121 8. Problem solving While proper information is needed form the problem, it is also recommended to try with latest application- and system software versions available. Software is continuously developed and default settings are improved (See Chapter 1.13 Compatibility issues in parameters between versions). Figure 48.
  • Page 124: Fault Codes

    122 · vacon Fault codes 9. Fault codes This chapter includes all the fault codes. However, some faults are not possible in the AFE mode. With other faults, the description can be different when compared to a standard AC drive. Over current fault The drive has detected a high current in the output phase.
  • Page 125 Fault codes vacon · 123 Earth fault Earth fault protection makes sure that the sum of the motor phase currents is 0. The over current protection is always working and protects the AC drive from earth faults with high currents. S1 = Sum of output phase current is not zero.
  • Page 126 124 · vacon Fault codes System Fault A system fault indicates that there are several different fault situations in the drive operation. S1 = Reserved Disturbance. Reset the unit and try again. If there is star coupler in the unit, check the fibre connections and phase order. Driver board or IGBT is broken.
  • Page 127 Fault codes vacon · 125 Undervoltage fault DC link voltage is below the fault voltage limit of the drive. S1 = DC link too low during the run. S2 = No data from the power unit. S3 = Undervoltage control supervision. Possible cause Too low a supply voltage.
  • Page 128 126 · vacon Fault codes Brake chopper supervision Brake chopper supervision generates pulses to the brake resistor for response. If no response is received within set limits, a fault is generated. Possible cause: No brake resistor is installed. The brake resistor is broken. Brake chopper failure.
  • Page 129 Fault codes vacon · 127 Counter fault Possible cause: Values displayed on the counters are incorrect. Correcting measures: Have a critical attitude towards values shown on the counters. Microprosessor watchdog fault Possible cause: Start-up of the drive has been prevented. Run request is ON when a new application is loaded to the drive Correcting measures: Reset the fault and restart.
  • Page 130 128 · vacon Fault codes IGBT temperature IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current. Possible cause: Too high a load. Identification run has not been made, which causes the motor to start undermagnetised. Correcting measures: Check the load.
  • Page 131 Fault codes vacon · 129 Device unknown An unknown option board or drive. S1 = Unknown device. S2 = Power1 not same type as Power2. Correcting measures: Contact your local distributor. IGBT temperature IGBT inverter bridge overtemperature protection has detected too high a short term overload current.
  • Page 132 130 · vacon Fault codes 4mA supervision Possible cause: Current at the analogue input is below 4mA. Signal source has failed. Control cable is broken or loose. Correcting measures: Check the current loop circuitry. External fault Possible cause: Digital input fault. Correcting measures: Remove fault situation from the external device.
  • Page 133 Fault codes vacon · 131 PT100 temperature fault The PT100 protection function is used to measure temperature and give a warning and/or a fault when the set limits are exceeded. The marine application supports two PT100 boards. One can be used for the motor winding and the other for the motor bearings.
  • Page 134 132 · vacon Fault codes Cooling Protection for the liquid-cooled units. An external sensor is connected to the drive (DI: Cooling Monitor) to indicate if cooling liquid is circulating. If the drive is in STOP state, only a warning is issued.
  • Page 135 Fault codes vacon · 133 Fieldbus communication fault on slot E Possible cause: The data connection between the fieldbus Master and the fieldbus board is broken. Watchdog pulse is missing from PLC, if Control Slot Selector is 0, or set for slot E. Correcting measures: Check installation.
  • Page 136 134 · vacon Fault codes Supply Frequency Supply frequency is not inside of set hysteresis, set in G2.9.7. Not to be confused with OPT-D7 protections that will give F93 D7 Frequency. Possible cause: Slow power increase in a grid and limit controllers activated. Power or current limits too low for the active load.
  • Page 137 Fault codes vacon · 135 Short Circuit Drive has operated against current limit for more than short circuit time. By phase fault detection has seen low voltage for more than short circuit time. Warning comes immediately when current is at current limit, fault comes after the short circuit time.
  • Page 138 Document ID: Vacon Ltd Member of the Danfoss Group Rev. B Runsorintie 7 65380 Vaasa Sales code: DOC-GRIDCONV+DLUK Finland...

Table of Contents