Disposal Instruction; Side-By-Side Installation; Mechanical Dimensions - Danfoss VLT Micro FC 51 Quick Manual

Hide thumbs Also See for VLT Micro FC 51:
Table of Contents

Advertisement

Quick Guide for VLT Micro FC 51

1.2.5 Disposal Instruction

1.3 Installation
1.3.1 Before Commencing Repair Work
1.
Disconnect FC 51 from mains (and external DC supply, if present.)
2.
Wait for 4 minutes (M1, M2 and M3) and 15 minutes (M4 and M5) for discharge of the DC-link.
3.
Disconnect DC bus terminals and brake terminals (if present)
4.
Remove motor cable

1.3.2 Side-by-Side Installation

The frequency converter can be mounted side-by-side for IP 20 rating units and requires 100 mm clearance above and
below for cooling. Please refer to the specifications near the end of this document for details on environmental ratings
of the frequency converter.

1.3.3 Mechanical Dimensions

A template for drilling can be found on the flap of the packaging.
Illustration 1.1: Mechanical dimensions.
Power (kW)
Frame 1 X 200-240 V 3 X 200 -240 V 3 X 380-480 V
M1
0.18 - 0.75
0.25 - 0.75
M2
1.5
1.5
M3
2.2
2.2 -3.7
M4
M5
1)
For LCP with potentiometer, please add 7.6 mm.
Table 1.1: Mechanical Dimensions
Equipment containing electrical components must not be disposed of together with do-
mestic waste.
It must be separately collected with electrical and electronic waste according to local and
currently valid legislation.
Height (mm)
A (incl. decoupling
A
0.37 - 0.75
150
1.5 - 2.2
176
3.0 - 7.5
239
11.0-15.0
292
18.5-22.0
335
®
MG.02.B5.02 - VLT
is a registered Danfoss trademark
Width (mm) Depth
a
B
plate)
205
140.4
70
230
166.4
75
294
226
90
347.5
272.4
125
387.5
315
165
1 Quick Guide
(mm) Max. Weight
1)
b
C
Kg
55
148
1.1
59
168
1.6
69
194
3.0
97
241
6.0
140
248
9.5