10.3.43 Fault Code 43 - Air Filter Clogged
Cause
Comparison with the set value of the internal cabinet air pressure: P
filter.
System default operation: Alarm
Troubleshooting
Check if the air filter is clogged.
Check if the air pressure sensor works normally.
10.3.44 Fault Code 44 - Cooling Fan Abnormal
Cause
Cooling fan motor winding overheating. To indicate this fault, the normally closed contact is opened.
System default operation: Alarm. System operation is configurable.
Troubleshooting
Check if the fan rotates in reverse direction.
Check if the fan is blocked.
10.3.45 Fault Code 45 - Fan Internal Power Loss
Cause
When the power of the cooling fan has a failure, the normally closed contact of the fan breaker is opened.
System default operation: Alarm. System operation is configurable.
Troubleshooting
Check the fan breaker.
Check whether the power supply circuit is normal.
10.3.46 Fault Code 46 - Fan External Power Loss
Cause
When there is a phase loss or undervoltage of the external fan power, this alarm is triggered.
System default operation: Alarm. System operation is configurable.
Troubleshooting
Check the wiring and voltage of the external fan power.
10.3.47 Fault Code 47 - Cooling Fan Failure
Cause
The fan breaker is tripped or fan interior thermal relay is opened.
System default operation: Alarm
Troubleshooting
Check the fan breaker.
Check if the thermal relay is opened.
Check if the fan is blocked.
10.3.48 Fault Code 48 - Transformer Overtemperature Alarm
Cause
The failure information is reported when the temperature of the transformer exceeds 95°C.
System default operation: Alarm
Troubleshooting
Check if the ambient temperature is too high.
Check that the cooling fans on top of the transformer are working normally.
Check if the air filter is clogged.
Check if the drive is in overload operation for a long time.
Check if the temperature sensor is in good condition.
102 | Danfoss A/S © 2021.06
< P
-25 pa. The reason can be the clogging of the air
under
set
Fault Tracing
AQ363633621020en-000201 / 172F3117