Danfoss VACON 1000 Operating Manual page 110

Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000
Operating Guide
Protections
Functions
Analog input
Analog output
Digital input/output
Human-machine interface
Display parameters
Communication interface
Communication protocol
Ambient temperature (opera-
Operation environ-
ment
tion)
Ambient temperature (stor-
age/transportation)
Relative humidity (operation)
Relative humidity (storage/
transportation)
Altitude
110 | Danfoss A/S © 2021.06
Input overcurrent, input phase loss, input power loss, input undervolt-
age, input overvoltage, input grounding, input sequence fault, output
overcurrent, output overload, output phase loss, output grounding,
output phase imbalance, output underload, electronic motor thermal
protection, motor stall, motor reverse, motor overspeed, motor under-
speed, speed setting analog loss, encoder abnormal, external fault,
current sensor power fault, input current sampling fault, output cur-
rent sampling fault, motor winding over temperature, motor bearing
overtemperature, air filter clogged, upstream main circuit breaker ab-
normal open, HV cabinet door open, control power loss, transformer
overtemperature, PLC-DSP communication failure, cooling fan abnor-
mal, UPS undervoltage, fan power loss, transformer temperature sen-
sor loss, PLC battery voltage low, PLC-HMI communication failure, up-
stream main circuit breaker close/open failure, startup cabinet switch
abnormal open, startup cabinet switch close/open failure, cooling fan
failure
Speed ramps selection, S-curve, frequency skip, multi-point V/F, torque
boost, AVR, dead-band compensation, Jog, flying start, DC braking,
field weakening, energy saving operation, droop control, speed feed-
forward control, overvoltage prevention during deceleration, power
cell symmetrical bypass, negative sequence compensation, input un-
dervoltage derating, low voltage ride through, automatic restart, syn-
chronous transfer, multi motor parameter storage, system auto bypass
0–10 V/4–20 mA, 2 channels
0–10 V/4–20 mA, 4 channels
7 sets input (standard, expandable)
10 sets output (standard, expandable)
7" touch screen (standard)
10" touch screen available as option
Target speed
Output speed
Input/output currents
Operation status indication
Standard: Modbus RTU
Options: PROFIBUS DP (DP-V0), DeviceNet
I/O, EtherNet/IP
, EtherCAT
®
MODBUS, PROFIBUS (optional)
0°C...+40°C (normal operation)
+40°C...+50°C (derated operation)
-40°C...+70°C
5–95%, no condensation
10–95%, no condensation
<1000 m (standard)
1000–2000 m (derating)
Specifications
, Modbus TCP, PROFINET
, CANopen
, POWERLINK, ControlNet
®
AQ363633621020en-000201 / 172F3117