VACON® 1000
Operating Guide
Termi-
Definition
nal
11
PE
12
MCB closed/open sta-
tus
13
14
MCB Trip
15
16
MCB Closing Allowed
17
18
PE
19
Ready
20
21
Running
22
23
HV Power on
24
25
Remote Mode/Local
Mode
26
27
Fault
28
29
Alarm
30
31
MCB trip 2
32
33
Exciting Current
Feedback
34
35
Speed Reference (AI)
36
37
Analog Output 1
38
39
Analog Output 2
40
41
Analog Output 3
42
56 | Danfoss A/S © 2021.06
Signal
Signal type
Grounding
DI
Normal open: Effective by closing
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
Grounding
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
DO
Normal open: Effective by closing
AI
+
-
AI
+
-
AO
+
-
AO
+
-
AO
+
-
Electrical Installation
Note
Standard configuration
Standard configuration
Standard configuration
Standard configuration
Standard configuration
Standard configuration
Standard configuration
Standard configuration
Standard configuration
Optional
Standard configuration.
0–10 V voltage signal or 4–20 mA current signal
according to requirements.
Standard configuration.
0–10 V voltage signal or 4–20 mA current signal
according to requirements.
If the analog output signal is voltage type, the
load impedance must be higher than 20 kΩ.
If the analog output signal is current type, the
load impedance must be lower than 500 Ω.
AQ363633621020en-000201 / 172F3117