VACON® 1000
Operating Guide
Maintenance
Maintenance
item
interval
UPS battery
Every 3 years
Every 3 months
HMI
Depending on
condition
High voltage
Every 4 years
electric display
device
Cooling fan
Every 4 years
Indicator
Every 5 years
Switching
Every 10 years
power supply
Power cells
1 year

9.4 Replacing the Air Filters

9.4.1 Air Filters of Standalone Cabinets

Procedure
1.
Loosen the screws on the air filter cover.
A
B
Illustration 69: Releasing the Filter Cover
A
Screws
82 | Danfoss A/S © 2021.06
Maintenance task
Check the heater and humidistat. Set the threshold of the humidistat below the ambient hu-
midity and check that the heater starts working. After testing, set the threshold to 80%.
Check the high voltage electric display light and that the second locked circuit is normal.
Check that the thermal relay setting value is correct.
Do a close test for the vacuum contactor or breaker, and check that the operation and feed-
back status is correct.
Check that the fuse and breaker is normal and there are no burn marks.
Change the battery every 3 years for reliable operation.
If the drive is stored for over 3 months and is not turned on during that time, charge the UPS
battery for 8 hours.
Charge spare storage batteries every 3 months.
The brightness of the HMI decays over time. The lifetime depends on the use conditions.
Change every 4 years for reliable operation.
Change every 4 years.
Change every 5 years.
Change every 10 years.
If a stored power cell has not been energized in the last 1 year, the electrolytic capacitors
must be reformed.
If the drive is stored for more than 2 years, high voltage cannot be applied directly to the
drive. Raise the input voltage gradually to wait until the capacitors are charged properly.
Maintenance
AQ363633621020en-000201 / 172F3117