3.6.3 Output Devices

See
3.3.6 Output Filter
Cabinet.

3.6.4 Mechanical Options

Heater Options +MHET/+MHEH
Table 5: Heater Options +MHET and +MHEH
Option
+MHET
Devices
Heater and thermostat
Application
Low operation temperature area (-5 °C...0 °C)
area
Purpose
To warm up the drive before turning it on if the tem-
perature is lower than 0 °C (but higher than -5 °C). The
low temperatures exceed the rated operation tempera-
ture of the micro chips and capacitors inside control
cabinet and power cells.
Location
Control cabinet and power cell cabinet
Key param-
Thermostat setting range: -10...50°C (14–122 °F), 0 °C as
eters
default preset value.
Heater power: 220 V, 400/150 W, depending on the
cabinet size.
Mechanical Interlocking System, +MMKI
See
8.6.2 Mechanical Interlocking
3.7 VACON® 1000 PC Tool
The VACON® 1000 PC Tool is an Ethernet-based computer-assisted software. Only one network cable is needed, and the monitoring
and fault diagnosis of the drive can be completed with this software.
The VACON® 1000 PC Tool integrates some auxiliary functions that are often used during normal operation and commissioning.
The status display panel shows the running status of the drive in real time.
The waveform display function allows the direct observation of the internal variables when the drive is running.
The parameter management function allows the direct modification or saving of the current system parameters on the comput-
er.
The fault analysis function can process the fault information in the DSP cache, list the fault content of the system, and the time
of occurrence, and show the waveform of the system input and output near the fault point.
In addition to these functions, the VACON® 1000 PC Tool also provides commissioning auxiliary functions and DSP program update
functions.
Minimum requirements for the VACON® 1000:
Operating system: Windows 10
Processor: Intel
Core
i5-6300U CPU @2.40 GHz 2.50 GHz
®
RAM: 8.00 GB
Danfoss A/S © 2021.06
System.
+MHEH
Heater and hygrostat
High relative humidity and condensation area
To prevent devices and cabinets from condensation and
corrosion in a high relative humidity operation environ-
ment, otherwise break down or flashover can occur dur-
ing operation.
Power cell cabinet, transformer cabinet, junction cabi-
net, or any other cabinets with high voltage parts
Hygrostat setting range: 35–95% RH, 80% as default pre-
set value.
Heater power: 220 V, 400/150 W, depending on the cabi-
net size.
AQ363633621020en-000201 / 172F3117 | 37