VACON® 1000
Operating Guide
System default operation: Coast stop. System operation is configurable.
Troubleshooting
Check the power grid voltage.
Reset the rated current of the motor.
Check the load and adjust the torque increase.
Select proper motor.
10.3.10 Fault Code 10 - Output Phase Loss
Cause
The software detects that the output phase from the drive to motor is disconnected.
System default operation: Coast stop. System operation is configurable.
Troubleshooting
Check if the output cables are loose or disconnected.
10.3.11 Fault Code 11 - Output Grounding
Cause
The software detects a grounding fault which is usually caused by an output grounding fault (phase-to-ground fault).
System default operation: Coast stop. System operation is configurable.
Troubleshooting
Check that the external cables and the motor are grounded.
Check the insulation of the motor and its cables.
10.3.12 Fault Code 12 - Output Phase Imbalance Alarm
Cause
During 10 minutes of continuous running time, the output imbalance is above 15‰ for a cumulative time of more than 30 s.
System default operation: Alarm. System operation is configurable.
Troubleshooting
Check that the capacitance of the DC-link capacitors matches the specifications.
Check that the voltage of the transformer secondary windings is balanced.
10.3.13 Fault Code 13 - Output Phase Imbalance Fault
Cause
The output imbalance is above 30‰ for over 1 s.
System default operation: Coast stop. System operation is configurable.
Troubleshooting
Check that the capacitance of the DC-link capacitors matches the specifications.
Check that the voltage of the transformer secondary windings is balanced.
10.3.14 Fault Code 14 - Output Underload
Cause
The software detects the motor operating in the underload area for longer than 20 s.
System default operation: Not detected. System operation is configurable.
Troubleshooting
Check if the load of motor is too light.
10.3.15 Fault Code 15 - Electronic Motor Thermal Protection
Cause
The calculated temperature or temperature rise is higher than the setting value.