Replacement Fuses - Danfoss VACON 1000 Operating Manual

Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000
Operating Guide
Cable/busbar
Motor connection cable
Grounding connection between cabinets
System grounding cable

11.4 Replacement Fuses

Table 31: Fuses in the Power Cell Cabinet for Standalone Type (Power Cell Current ≤215 A)
Power cell current rating
36 A
50 A
70 A
100 A
Danfoss A/S © 2021.06
Cable/busbar size
Terminal type
600 kcmil
TLK400-12
750 kcmil
TLK400-12
9 AWG
TLK10-8
5 AWG
TLK25-8
2 AWG
TLK35-8
2/0 AWG
TLK70-8
3/0 AWG
TLK95-10
4/0 AWG
TLK120-10
250 kcmil
TLK150-10
300 kcmil
TLK185-10
400 kcmil
TLK240-10
600 kcmil
TLK400-12
750 kcmil
TLK400-12
2
75 mm
N/A
2
120 mm
N/A
2
200 mm
N/A
2
300 mm
N/A
2
100 mm
TLK120-8
Fuse model
170M1367
170M2614
170M4810
170M1368
170M2615
170M4811
170M1369
170M2616
170M4812
170M1371
170M2618
Specifications
Screw type
Tightening torque (Nm)
M10×35
30.0–50.0
M10×35
30.0–50.0
M8×25
12.0–15.0
M8×25
12.0–15.0
M8×25
12.0–15.0
M8×25
12.0–15.0
M10×35
30.0–50.0
M10×35
30.0–50.0
M10×35
30.0–50.0
M10×35
30.0–50.0
M10×35
30.0–50.0
M10×35
30.0–50.0
M10×35
30.0–50.0
M8×25
12.0–15.0
M8×25
12.0–15.0
M8×25
12.0–15.0
M8×25
12.0–15.0
M8×20
12.0–15.0
Fuse rating
700 V AC, 100 A
700 V AC, 100 A
1000 V AC, 100 A
700 V AC, 125 A
700 V AC, 125 A
1000 V AC, 125 A
700 V AC, 160 A
700 V AC, 160 A
1000 V AC, 160 A
700 V AC, 250 A
700 V AC, 250 A
AQ363633621020en-000201 / 172F3117 | 135