System default operation: Coast stop
Troubleshooting
Check the fault record.
10.3.29 Fault Code 29 - Flying Start Failure
Cause
During flying start, a speed search failure occurs or any other fault is generated.
System default operation: Coast stop
Troubleshooting
If a speed search failure caused the flying start failure, check the parameter of the flying start result for the reason for the flying
start failure.
If some other fault caused the flying start failure, check the fault record.
10.3.30 Fault Code 30 - Automatic Restart Failure
Cause
During the trial time of the automatic restart, the number of faults is higher than the maximum number of trials, or a permanent
fault occurs.
System default operation: Trip
Troubleshooting
Check the fault record.
10.3.31 Fault Code 31 - Synchronous Transfer Failure
Cause
One of the following occurs during synchronous transfer:
Switch status/close/open failure.
Speed stable timeout. Caused by load fluctuation, which can occur during acceleration to grid frequency in the drive to grid
synchronization process.
Voltage synchronous timeout. Caused by electric network fluctuation, which can occur during the voltage synchronization
process.
Load transfer timeout. Caused by load fluctuation, which can occur during the load transfer process.
System default operation: Trip
Troubleshooting
If there is a switch status/close/open failure:
-
Check the status of the switches.
-
Check the wiring of the digital inputs/outputs.
-
Make sure that there are no problems with the breaker.
If there is a speed stable timeout, modify parameter "Speed err threshold of synchronous transfer" (P0772).
If there is a voltage synchronous timeout, modify one of these parameters:
-
"Phase error threshold of synchronous transfer" (P0767)
-
"Voltage error threshold of synchronous transfer" (P0771)
-
"Maximum voltage synchronize time of synchronous transfer" (P0778)
If there is a load transfer timeout, modify one of these parameters:
-
"Current error threshold of synchronous transfer" (P0353)
-
"Maximum load transfer time of synchronous transfer" (P0779)
10.3.32 Fault Code 32 - Failure Of Motor Selection
Cause
The serial number of selected motor is wrong.
Danfoss A/S © 2021.06
Fault Tracing
AQ363633621020en-000201 / 172F3117 | 99