Specifications; Technical Data - Danfoss VACON 1000 Operating Manual

Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000
Operating Guide

11 Specifications

11.1 Technical Data

Table 14: Technical Data for VACON® 1000
System technology
Topology type
Technology
Inverter configuration
Input
Voltage range
Input frequency
Input voltage tolerance
Input voltage sag
Short-circuit current rating
(SCCR)
Control voltage with circuit
protection
Control power
Input current distortion
Input current THD
Input voltage THD
Input impedance device
Input transformer
Transformer type of construc-
tion
Transformer insulation type
Transformer inrush current
limitation
Transformer secondary for
auxiliaries
Temperature sensors in trans-
former windings
Grounding
Grounding system
Ground busbar
Output voltage range
Output
Output current THDi (1st...
49th)
108 | Danfoss A/S © 2021.06
Multilevel IGBT topology (Cascade H-Bridge)
Voltage source inverter (VSI)
Pulse-width modulated (PWM) power modules
-10%...+10% (normal operation)
-10%...-30% (derated continuous operation)
50/60 Hz (±5% transients)
±10% of nominal, unbalance up to 3% per IEC 610002-4
-30% of nominal without tripping
Continuous operation with reduced power, derated power 70–90%.
31.5 kA, 100 ms
1-phase 230 V AC, 50 Hz
1-phase 220 V AC, 60 Hz
1-phase AC 120–240 V
3-phase AC 240–480 V
Capacity 5 kVA (other voltages available)
Meets IEEE 519 standard, without input filter
<5% (at rated load)
<5% (at rated load)
Multiphase isolation transformer integrated into the drive
Dry type, phase shifting, Cu/Cu; Forced air cooling
Al/Cu or Al/Al available as an engineered option.
Class 180 (H)
I
>215 A limited with start-up cabinet (optional, +PSTC)
n
3-phase, 460 V AC with neutral and with a 380 V AC tap, 50/60 Hz
3x PT100, one in each winding
As per IEC61936-1
Tin-plated grounding busbar section
2.4–11 kV
<2% at rated speed
Specifications
AQ363633621020en-000201 / 172F3117