Page 1
Drives and Controls Frequency converters Frequency Converter ® 6000 Quick Setup Installation Setting Operation ® is a trademark of Danfoss A/S...
Page 2
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains. Using VLT 6002-6005: wait at least 4 minutes Using VLT 6006-6275: wait at least 15 minutes MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 3
EMC properties of the in the 50-1000 V AC and 75-1500 V DC appliance, system or installation rests with the voltage ranges. Danfoss provides its installer. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 4
All the above-mentioned units require a side by side without any space, since these units minimum space of 100 mm above and below do not require any cooling on the sides. the enclosure. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 5
This applies to IP 00, IP 20 and IP 54 units alike. All IP 00 and IP 20 units in the above-mentioned series can be installed side by side without any spacing. MG.60.C4.02 – VLT is a registered Danfoss trademark VLT 6075-6275 IP 54...
Page 6
Remember that all interference-filled in- or possible and by using the greatest possible outgoing cables to/from a cabinet should be surface area. A flat conductor, for example, screened/armoured or filtered. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 7
In the case of an earth fault, a DC content may considered low-voltage terminals with basic develop in the faulty current. galvanic isolation. In addition, the VLT 6000 Never use ELCB relays, type A, since such HVAC EMC performance will be reduced if relays are not suitable for DC fault currents.
Page 8
Allowance must be made for the pressure loss across the filters and for the fact that the pressure is going to drop as the filters are choked. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 9
61. This terminal is connected to earth via an internal RC link. It is recommended to use twisted-pair cables to reduce the differential mode interference between the conductors. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 10
0.5 - 0.6 Nm VLT 6016-6027 1.8 Nm VLT 6032-6062 3.0 Nm VLT type Tightening-up Bolt 3 x 380-460 V torque size VLT 6075-6125 11.3 Nm VLT 6150-6275 11.3 Nm VLT 6350-6550 42.0 Nm MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 11
U, V, W Earth connection. No. 99 All types of three-phase asynchronous standard motors can be used with a VLT 6000 HVAC unit. Small-size motors are normally star-connected. The factory setting is for clockwise rotation with (220/380 V, ∆/Y). Large-size motors are delta- the VLT frequency transformer output connected connected (380/660 V, ∆/Y).
Page 12
It is important to keep the motor cable as short as possible so as to reduce the VLT 6000 HVAC is able to control several noise level and leakage currents to a minimum. motors connected in parallel. If the motors...
Page 13
DC source. In addition, a 12- pulse option can be connected to reduce the total harmonic distortion. Nos. 88, 89 Terminal nos. Contact Danfoss if you require further information. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 14
VLT frequency converter can be be connected to terminals 88 and 89. Please controlled and monitored via serial ask Danfoss for a Design Guide to learn more. communication. Analogue inputs can be connected to terminals 53 [V], 54 [V] and 60 [mA]. These inputs can be programmed for either reference, feedback or thermistor.
Page 15
55 by means of a three-wire transmitter. Analogue/digital outputs for 42, 45 indicating frequency, reference, current and torque. See parameters 319-322 Analogue/ digital outputs. Supply voltage to potentiometer and thermistor 10 V DC. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 16
- LCP (Local Control for voltage (ON), warning (WARNING) and Panel). This is a complete interface for alarm (ALARM), respectively. operation and programming of the VLT 6000 All VLT frequency converter parameter Setups HVAC. can be changed immediately via the control...
Page 17
The VLT frequency converter will (trip). Can be selected as Enable [1] or start the motor, since a start Disable [0] via parameter 015 Reset command is given by means of on LCP. [HAND START]. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 18
Three operating data values can be shown in the first display line, while one operating variable can be shown in the second display line. To be programmed via parameters 007, 008, 009 and 010 Display readout. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 19
® 6000 HVAC Display mode I: Ž Status line: VLT 6000 HVAC offers different display modes depending on the mode selected for the VLT 80.0% 5.08A frequency converter. The figure on the next page shows the way to navigate between different 40.0Hz...
Page 20
In the second line, operating data 2 remains unchanged. When the key is released, the different operating data values are shown. REF% CURR.A 50.0Hz SETUP AUTO REMOTE RUNNING MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 21
AUTO REMOTE RUNNING With local ----- 60 reference HAND LOCAL RUNNING Keep the [DISPLAY Display mode MODE] key down Display mode IV REF% CURR.A POW.,KW 40.0Hz SETUP AUTO REMOTE RUNNING Display mode III MG.60.C4.02 – VLT is a registered Danfoss trademark...
MOTOR CURRENT 3.90 A SETUP 210 REFERENCE The functional value flashes until signing off by pressing the [OK] button. The functional value has now been selected. Use [CANCEL] to cancel the change. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 23
600, Operating hours 601, Hours run 602, kWh counter 603, Number of power-ups 604, Number of overtemperatures 605, Number of overvoltages It is also possible to carry out initialisation via parameter 620 Operating mode. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 24
® 6000 HVAC MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 25
Quick menu The [QUICK MENU] key gives access to the 12 1 of 12 most important parameters of the VLT frequency converter. LANGUAGE After programming, the VLT frequency converter will in most par. 001 cases be ready 2 of 12 for operation.
Page 26
Quick menu: Parameter 7 of 12 Quick menu: Parameter 1 of 12 Used to select the language for the display. Used to select a minimum frequency limit, corresponding to the lowest frequency at which the Quick menu: Parameter 2 of 12 motor is to run.
Page 27
Freeze output has been enabled via a digital Remote reference (REM.) input. If REMOTE has been selected, the reference is set via the control terminals or via serial communication. See also Display modes. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 28
DRIVE ready (UN. READY) The VLT frequency converter is ready for operation, but terminal 27 is a logic ‘0’ and/or a Coasting command has been received via the serial communi-cation. MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 29
Feedback low (FEEDBACK < FDB LOW) Feedback high (FEEDBACK > FDB HIGH) Reference low (REF. < REF. LOW) Reference high (REF. > REF. HIGH) Temperature auto derate (TEMP.AUTO DERATE) Unknown fault (UNKNOWN ALARM) MG.60.C4.02 – VLT is a registered Danfoss trademark...
Page 30
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
Need help?
Do you have a question about the VLT 6000 and is the answer not in the manual?
Questions and answers