Program Example Using The Utility Package - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

6 PROGRAMMING

6.2.1 Program example using the utility package

6 - 5
(1) Operation of utility package
(a) Initial setting (refer to Section 5.4)
<When cascade control is not executed>
CH1 Input range ........................................................."0"
CH2 Unused channel setting ....................................."Not Used"
[Limiter setting]
CH1 Upper setting limiter..........................................."2000"
CH1 Lower setting limiter..........................................."0"
[Alert function setting]
CH1 Alert 1 mode setting..........................................."Upper limit input"
CH1 Alert set value 1 ................................................."1800"
[Normal control setting]
CH1 Set value (SV) setting ........................................"800"
[Program control setting]
CH1 Execution pattern ..............................................."Program Pattern 1"
CH1 Time scale.........................................................."1s"
CH1 Program pattern 1
Final segment....................................................."4"
Segment 1 Set value (SV) setting ....................."1500"
Segment 1 Executing time................................."200"
Segment 1 Zone PID data No. ........................."2"
Segment 2 Set value (SV) setting ....................."1500"
Segment 2 Executing time................................."100"
Segment 2 Zone PID data No. .........................."2"
Segment 3 Set value (SV) setting ....................."500"
Segment 3 Executing time................................."100"
Segment 3 Zone PID data No. .........................."1"
Segment 4 Set value (SV) setting ....................."500"
Segment 4 Executing time................................."100"
Segment 4 Zone PID data No. .........................."1"
<When cascade control is executed>
CH1 Input range ........................................................."0"
CH2 Input range ........................................................."0"
CH1 Unused channel setting ....................................."Used"
CH2 Unused channel setting ....................................."Used"
[Limiter setting]
CH1 Upper setting limiter..........................................."2000"
CH1 Lower setting limiter..........................................."0"
CH2 Upper setting limiter..........................................."2000"
CH2 Lower setting limiter..........................................."0"
[Normal control setting]
CH1 Set value (SV) setting ........................................"1000"
MELSEC-Q