Execution Pattern (Buffer Memory Address 272, 528: Un\G272, Un\G528); Start Mode (Buffer Memory Address 273, 529: Un\G273, Un\G529) - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.5.64 Execution pattern (buffer memory address 272, 528: Un\G272, Un\G528)

3.5.65 Start mode (buffer memory address 273, 529: Un\G273, Un\G529)

3 - 108
This setting is available only in the setting mode. However, when the parameter
change in program control function is enabled, this setting can be changed in the
operation mode also. For details on the parameter change in program control
function, refer to Section 3.2.18.
To activate the change, turn on Setting change command (YnB).
(1) This setting specifies the program pattern to be executed in the program control.
(2) The following lists the setting values.
• Program pattern 1: Set 1 (default).
• Program pattern 2: Set 2.
• Program pattern 3: Set 3.
This setting is available only in the setting mode. However, when the parameter
change in program control function is enabled, this setting can be changed in the
operation mode also. For details on the parameter change in program control
function, refer to Section 3.2.18.
To activate the change, turn on Setting change command (YnB).
(1)
A starting method of the set value (SV) at program control start can be selected
from the following.
• Zero start: Set 0 (default).
• PV start 1 (time fixed): Set 1.
• PV start 2 (time shortened): Set 2.
• PV start 3 (time shortened/find type): Set 3.
• SV start: Set 4.
For details on each starting method, refer to Section 3.2.12 (2).