(2) Indication accuracy
Table 3.3 and Table 3.4 list the indication accuracy against ambient
temperature.
(a) At ambient temperature 23 2
Table 3.3 Indication accuracy at ambient temperature 23 2
Item
K, J, T,
E, PLII
S, R, N,
Thermocouple
W5Re/
W26Re
B
Micro voltage
Voltage
Current
(b) At ambient temperature 0 to 55
Table 3.4 Indication accuracy at ambient temperature 0 to 55
Item
K, J, T,
E, PLII
S, R, N,
Thermocouple
W5Re/
W26Re
B
Micro voltage
Voltage
Current
Less than -100
-100 to less than 500
500
or more
-50 to less than 1000
1000
or more
Less than 400
400 to less than 1000
1000
or more
Full-scale
Less than -100
-100 to less than 500
500
or more
-50 to less than 1000
1000
or more
Less than 400
400 to less than 1000
1000
or more
Full-scale
MELSEC-Q
Error
1.0
0.5
(Indication value
(0.1%) +1 digit)
1.0
(Indication value
(0.1%) +1 digit)
70.0
1.0
(Indication value
(0.1%) +1 digit)
( 0.1%)
Error
2.0
1.0
(Indication value
(0.2%) +1 digit)
2.0
(Indication value
(0.2%) +1 digit)
140.0
2.0
(Indication value
(0.2%) +1 digit)
( 0.2%)