Mitsubishi Electric MELSEC-Q Series User Manual page 60

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS
Buffer memory area
name
Execution pattern
Start mode
Time scale
Set value at program
control start (SV_PCS)
setting
• Program pattern data
3 - 25
The following gives the detailed explanation of control data, program pattern, and
zone PID data.
(a) Control data
Common data required for executing the program control are set.
Select a program pattern to be executed from the
program patterns 1 to 3.
Set a starting method of the set value (SV) at a
control start. For details, refer to (2) in this section.
Set the execution time unit of each segment set in
program pattern data.
Set the set value (SV) at a program control start
when a starting method is specified. For details,
refer to (2) in this section.
(b) Program pattern data
A program pattern consists of segments, which have a set value (SV), executing
time (execution time), and zone PID data No.
The Q62HLC can set three patterns of program pattern data with up to 16
segments.
Several program patterns can be linked by pattern link (refer to the next page for
buffer memory areas).
Description
MELSEC-Q
Buffer memory address (decimal)
CH1
CH2
272
528
273
529
274
530
501
757
3 - 25