Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

6 PROGRAMMING
Device
X0
Setting value write command
PID constant read command from FeRAM
(when GX Configurator-TC is used)
X1
Auto tuning execution command
(when GX Configurator-TC is not used)
X2
Error code reset command
X3
Setting mode switching command
X4
Normal control mode switching command
X5
Program control mode switching command
X7
Manual control mode 2 switching command
X8
Cascade control switching command
X11
Program control auto tuning execution command
X12
Program control pattern data setting command
X15
Cascade control setting command
X20 to X2F Manual output setting
Y40 to Y4F Error code output
Y50 to Y5F Measured value output
FeRAM read failure output
(when GX Configurator-TC is used)
Y60
FeRAM write failure output
(when GX Configurator-TC is not used)
D50
Error code
D51
Measured value
6 - 3
(a) Devices used by user
Function
When turning on the setting value write command X0, the parameters,
which are set in this program example, are as follows.
• CH2 Unused channel setting
• CH1 Input range
• CH1 Alert 1 mode setting
• CH1 Alert set value 1
• CH1 Set value setting
• CH1 Upper setting limiter
• CH1 Lower setting limiter
When program control is used, turn on X0 after turning on X12 (program
control pattern data setting command).
*1: PID constants of zone 1 and zone 2 that are used for program control are set.
By turning on X11, the auto tuning is executed after switching into normal control mode.
Then, PID constant of zone is set when the auto tuning ends.
Sets the parameter to execute normal control and program control using
CH 1 and writes into FeRAM.
Reads PID constant set by auto tuning from FeRAM.
Executes auto tuning for the specified set value.
Operates only in the normal control mode.
Clears (0) error codes.
Switches into the setting mode by turning off then on.
Switches into the normal control mode by turning off then on.
Needs to set parameters for normal control before switching.
Switches into the program control mode by turning off then on.
Needs to set parameters for program control before switching.
Switches into the manual control mode 2 by turning off then on.
After the switching, the operation is performed by the values of manual
output settings (X20 to X2F).
Switches into the cascade control mode by turning off then on.
Needs to set parameters for cascade control before switching.
Executes auto tuning for program control.
Sets the pattern data for executing program control.
Sets parameters for executing cascade control.
Specifies the manipulated value (MV) when manual control mode 2 is
operated.
Outputs error codes as BCD value.
Outputs measured value as BCD value.
Outputs when reading from FeRAM has failed.
Outputs when writing into FeRAM has failed.
Stores error codes that are read out when the error has occurred.
Stores measured values that are read out.
: 1 (Unused. However, set "used"
: 0 (K: -200 to 1372 )
: 1 (UprLmt Input Alert)
: 1800 (180 )
: 800 (80 )
: 2000 (200 )
: 0 (0 )
MELSEC-Q
Description
*1
*2
*3
when used for cascade control. In
this case, parameter is set to the
same as CH1.)
6 - 3