3 SPECIFICATIONS

3.5.49 Command advancing (buffer memory address 202, 218: Un\G202, Un\G218)

Command advancing
(Buffer memory address: 202, 218)
Advancing completion flag
(Buffer memory address: 263, 519)
3.5.50 SV tracking setting (buffer memory address 203, 219: Un\G203, Un\G219)
3 - 104
(1) This is the command of the advancing operation to carry the progress of the
program control forward to the next segment.
• Advancing OFF
• Advancing ON
Set value
Fast-
forward
Segment 1
0
0
(2) The completion of the advancing operation can be checked in Advancing
completion flag (buffer memory address: 263, 519).
(3) This command is disabled when the program control is in the hold status.
(1) Whether to use the SV tracking function or not is set.
• Disable SV tracking: Set 0 (default).
• Enable SV tracking: Set 1.
: Set 0 (default).
The advancing operation is not performed.
: Set 1.
The advancing operation is performed. The progress of
the program is advanced by one segment and the
program starts from the next segment.
Execute
from here
Command advancing ON
Segment 2
Segment 3
1
1
MELSEC-Q
Time
Segment 4
0
0
3 - 104