4 PROCEDURES AND SETTINGS BEFORE SYSTEM OPERATION
4 - 9
(2) Operating procedure
Start the settings with GX Developer I/O assignment setting window.
REMARKS
Do not set the "error-time output mode" and "hardware error-time CPU operation
mode" in the intelligent function module detailed setting as they are invalid for the
Q62HLC.
(a) I/O assignment window
Specify the following for the slot where the Q62HLC
is mounted.
Type
: Select "Intelli."
Model name : Enter the module's model name.
Points
: Select 16 points.
Start XY
: Enter the start I/O signal for the
Q62HLC.
(b) Switch setting for I/O and intelligent function module
Click on Switch Setting on the I/O assignment
setting window to display the window at the left and
set switches 1 to 5.
The setting can easily be done if values are entered
in hexadecimal. Change the input format to
hexadecimal and enter values.
MELSEC-Q
4 - 9