Forced Output Command (Buffer Memory Address 204, 220: Un\G204, Un\G220); Forced Output Manipulated Value (Mv) (Buffer Memory Address 205, 221: Un\G205, Un\G221); Segment Monitor (Buffer Memory Address 256, 512: Un\G256, Un\G512); Segment Remaining Time (Buffer Memory Address 257, 513: Un\G257, Un\G513) - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.5.51 Forced output command (buffer memory address 204, 220: Un\G204, Un\G220)

3.5.52 Forced output manipulated value (MV) (buffer memory address 205, 221: Un\G205,
Un\G221)

3.5.53 Segment monitor (buffer memory address 256, 512: Un\G256, Un\G512)

3.5.54 Segment remaining time (buffer memory address 257, 513: Un\G257, Un\G513)

3 - 105
(1) This is the command to execute the forced output function.
• Forced output not commanded: Set 0 (default).
• Forced output commanded: Set 1. The forced output function is executed.
(2) The status of the forced output function can be checked in Forced output status
flag (buffer memory address: 266, 522).
(3) This command is enabled only when the bit 0 of the switch 3 is set to 1 (Enable)
in the intelligent function module switch setting.
(1) The manipulated value (MV) targeted for forced output is set when forced output
is executed in normal control mode, manual control mode 1, program control
mode, or manual control mode 2.
(2) The setting range is -200 to 4200. If values -32768 to -201 are set, the analog
output values become close to 0mA.
For relationship of the setting value in this area, Manipulated value (MV) (buffer
memory address: 13, 14), and analog output value, refer to Section 3.2.16 (3).
(3) This setting is enabled only when the bit 0 of the switch 3 is set to 1 (Enable) in
the intelligent function module switch setting.
(4) Check that Forced output status flag (buffer memory address: 266, 522) is 1
(With forced output command) before writing data into this area.
(1) The currently operated segment No. is stored.
The stored values are 1 to 16.
(1) The remaining time of the currently operated segment is stored.
(2) The time scale of the segment remaining time is the scale set in Time scale
(buffer memory address: 274, 530) (refer to Section 3.5.66).
MELSEC-Q
3 - 105