At Differential Gap (Buffer Memory Address 46, 78: Un\G46, Un\G78); At Additional Lag (Buffer Memory Address 47, 79: Un\G47, Un\G79) - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.5.19 AT differential gap (buffer memory address 46, 78: Un\G46, Un\G78)

3.5.20 AT additional lag (buffer memory address 47, 79: Un\G47, Un\G79)

3 - 89
(1) The waiting time required from the output on/off status change to the next status
change during auto tuning is set.
(2) The setting range is 0 to 10000 (0.00 to 100.00s).
(3) The target setting value for standard mode is 10 (0.1s), for fast response mode
is 1 (0.01s).
Measured value
Set value (SV)
Output
(1) The waiting time required for the output on/off status being changed after the
measured value (PV) has passed the set value (SV) during auto tuning is set.
(2) The setting range is 0 to 1000 (0.00 to 10.00s).
(3) The target setting value for standard mode is 10 (0.1s), for fast response mode
is 1 (0.01s).
Measured value
Set value (SV)
Output
Measured
value (PV)
AT difference gap
Measured value
(PV)
AT additional lag
MELSEC-Q
Time
Time