3 SPECIFICATIONS
• When Forced output manipulated value (MV) (buffer memory address: 205, 221) is
changed during forced output processing, the change is reflected to the manipulated
value (MV) immediately. (Bumpless shifting does not operate.)
• When Forced output command (buffer memory address: 204, 220) is changed to 0
(Forced output not commanded) during forced output processing, bumpless shifting
operates gradually changing back to the original operation by each control output
update cycle.
• The forced output function cannot be used during auto tuning. Even if Forced output
command (buffer memory address: 204, 220) is changed to 1 (Forced output
commanded), Forced output status flag (buffer memory address: 266, 522) does not
become 1 (Forced output not commanded).
• Even if Auto tuning start command (Yn4, Yn5) is turned on during forced output
processing, auto tuning is not executed. At this time, an error does not occur.
3 - 47
(4) Operation during program control
When Forced output command (buffer memory address: 204, 220) is set to 1
(Forced output commanded) while Program control run/reset (buffer memory
address: 57, 89) is 1(RUN), the module goes into a forced output status.
Meanwhile, the program control operation continues inside the module.
When the value in Forced output command (buffer memory address: 204, 220)
is set to 0 (Forced output not commanded), the mode returns to the program
control mode. The program control resumes operation that continued while
forced output was in execution.
POINT
MELSEC-Q
3 - 47