Mitsubishi Electric MELSEC-Q Series User Manual page 65

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS
Buffer memory
area name
Upper limit
Proportional band
(P) setting
Integral time (I)
Derivative time (D)
Control response
parameter
3 - 30
Description
Sets the upper limit
for each zone to
divide input range
into zones.
Sets the constants
of proportional
band (P) for zones.
Sets the constants
of integral time (I)
for zones.
Sets the constants
of derivative time
(D) for zones.
Sets the 3-step
responses to the
set value change
of PID control.
(2) Program control starting method
A starting method of program control can be selected. Set one of the following
starting methods in Start mode (buffer memory address: 273, 529).
• 0: Zero start
• 1: PV start 1 (time fixed)
• 2: PV start 2 (time shortened)
• 3: PV start 3 (time shortened/find type)
• 4: SV start
CH
Buffer memory address (decimal)
1
2
3
1
275
276
277
2
531
532
533
1
282
286
290
2
538
542
546
1
283
287
291
2
539
543
547
1
284
288
292
2
540
544
548
1
285
289
293
2
541
545
549
MELSEC-Q
Zone
4
5
6
7
278
279
280
281
534
535
536
537
294
298
302
306
550
554
558
562
295
299
303
307
551
555
559
563
296
300
304
308
552
556
560
564
297
301
305
309
553
557
561
565
8
-
-
310
566
311
567
312
568
313
569
3 - 30