3 SPECIFICATIONS
3 - 36
(c) Operation at the completion of program control
After the PID control of the final segment set by the final segment completes
and reaches the pattern end, the pattern end output is performed.
• The pattern end output continues the PID control at the set value of the
final segment for the time set in Output time setting of pattern end (buffer
memory address: 323, 387, 451, 579, 643, 707).
• During the pattern end output, 1 is stored in Pattern end output flag (buffer
memory address: 259, 515).
• After the completion of the pattern end output, the program control
completes, 1 is stored in End status flag (buffer memory address: 260,
516), and the program control becomes a RESET status.
• At the RESET status, the PID control is stopped, the set value becomes 0,
and the output turns off
*4: The current value output at the RESET status is the value set in Lower
output limiter (buffer memory address: 43, 75).
POINT
To execute the program control in a row, wait for more than 0.05 second after the
status of the first program control changes to RESET, and then set 1 (RUN) in
Program control run/reset (buffer memory address: 57, 89).
*4
.
MELSEC-Q
3 - 36