Advancing Completion Flag (Buffer Memory Address 263, 519: Un\G263, Un\G519); Execution Pattern Monitor (Buffer Memory Address 264, 520: Un\G264, Un\G520); Zone Pid Monitor (Buffer Memory Address 265, 521: Un\G265, Un\G521); Forced Output Status Flag (Buffer Memory Address 266, 522: Un\G266, Un\G522) - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.5.60 Advancing completion flag (buffer memory address 263, 519: Un\G263, Un\G519)

3.5.61 Execution pattern monitor (buffer memory address 264, 520: Un\G264, Un\G520)

3.5.62 Zone PID monitor (buffer memory address 265, 521: Un\G265, Un\G521)

3.5.63 Forced output status flag (buffer memory address 266, 522: Un\G266, Un\G522)

3 - 107
(1) This is a flag to check if the advancing operation according to the setting in
Command advancing (buffer memory address: 202, 218) is completed in the
program control.
• Advancing operation uncompleted or no command: 0 is stored.
• Advancing operation completed: 1 is stored.
(2) This flag is reset to 0 by turning off the command advancing.
(1) For program control, the program pattern No. in execution is stored.
When program control is in RUN, values are stored as follows.
• Pattern 1: 1 is stored.
• Pattern 2: 2 is stored.
• Pattern 3: 3 is stored.
When program control is in RESET, 0 (default value) is stored.
(1) The zone No. of the zone PID data used for the control in the program control is
stored.
• Zone 1: 1 is stored.
• Zone 2: 2 is stored.
• Zone 3: 3 is stored.
• Zone 4: 4 is stored.
• Zone 5: 5 is stored.
• Zone 6: 6 is stored.
• Zone 7: 7 is stored.
• Zone 8: 8 is stored.
When program control is in RESET, 0 (default value) is stored.
(1) This is a flag to check the status of the forced output command.
• Forced output not commanded: 0 (default value) is stored.
• With forced output command: 1 is stored.
(2) Changing Forced output command (buffer memory address: 204, 220) from 1
(Forced output commanded) to 0 (Forced output not commanded) resets this
flag to 0.