Detection Scenarios
Root Causes
Possible CRU Replacements
Possible FRU Replacements
Resolution
T020: Cannot calibrate storage, motion OK
Description
Detection Scenarios
Root Causes
|
|
Possible FRU Replacements
Resolution
11-12
TS3310 Tape Library Setup and Operator Guide
Calibration motion completes but edge finding of one or
more edges does not occur.
1. Calibration sensor not functioning properly.
2. Calibration target not functioning properly.
3. Drive or Picker position is so far off nominal that search
pattern cannot locate target.
Drive Sled
v Y Motor
v Y-axis Assembly
v Y-axis Cable Spool
v Picker Assembly
v Internal Cables and Boards Kit
Before replacing a library component, refer to "Diagnosing
a Problem" on page 10-2 for additional diagnostic
procedures.
If the problem can not be resolved using the information in
this document, perform "DR021: Contact Service" on page
11-41
System cannot successfully calibrate the position of a
storage magazine but the calibration search pattern
completes successfully.
Calibration motion completes but edge finding of one or
more edges does not occur.
1. Calibration sensor not functioning properly.
2. Calibration target not functioning properly.
3. Drive or Picker position is so far off nominal that search
pattern cannot locate target. This can also generate a
T083: Picker Assembly not level.
4. The Picker Lock mechanism is not in the appropriate
unengaged position.
v Fiducial Targets
v Y Motor
v Y-axis Assembly
v Y-axis Cable Spool
v Picker Assembly
v Internal Cables and Boards Kit
Before replacing a library component or contacting IBM
Technical Support, refer to "Diagnosing a Problem" on
page 10-2 for additional diagnostic procedures.
If the problem can not be resolved using the information in
this document, perform "DR021: Contact Service" on page
11-41.