Installing and setting up PCU Base for IPC
10.3 Configuration of the system
3. Switch to the "Floating operation" tab and make the following settings:
– Deactivate the "Display monitoring window after" checkbox
– Click directly in the text field at "Start application after" and specify the path of
– After you have specified the path of the USVShutdown.bat, activate the "Start
4. Confirm the settings with "Save".
Parameterizing a delay time for quitting the HMI software
Before the SITOP monitor closes Windows, USVShutdown.bat shuts down operation of the
HMI software.
If the HMI software cannot be shut down within 180 seconds (factory setting) due to an error,
HMI software shutdown is forced and Windows is shut down.
194
Note
Deactivating the monitoring window
Display of the monitoring window can cause malfunctioning of the HMI software.
the USVShutdown.bat:
C:\Program Files (x86)\Siemens\MotionControl\siemens\sinumerik
\hmi\base\USVShutdown.bat
Note
Do not use the "Browse" button
The dialog can crash if you use the "Browse" button to specify the path of
the USVShutdown.bat.
Instead, enter the path directly in the text field.
application after" checkbox. Optionally, you can specify the wait time after which
the USVShutdown.bat is to be executed (e.g. 5 seconds).
MCU commissioning: NC, PLC, Drive