6.4 Cable cross-sections

Device Type
Size
Mains voltage 115 V
Supply voltage (50/60 Hz) U
LN
U
115 V AC, single-phase / U
e
DC1-1D2D3...
FS1
DC1-1D4D3...
FS1
DC1-1D5D8...
FS2
Mains voltage 230 V
Supply voltage (50/60 Hz) U
LN
U
230 V AC, single-phase / U
e
DC1-122D3...
FS1
DC1-124D3...
FS1
DC1-127D0NN...
FS1
DC1-127D0FN...
FS1
DC1-127D0NB...
FS2
DC1-127D0FB...
FS2
DC1-12011...
FS2
DC1-12015...
FS3
The "Maximum terminal capacity" specification indicates the maximum
possible sizes that can be connected to the power terminals. The cross-
sectional areas and gauges that should be used for the power supply and
motor connections are recommendations for the corresponding frame sizes
and ratings and are provided as examples.
Use the general installation instructions and local conditions as a
basis when selecting terminal capacities.
Table 36: Cable cross-sections
Maximum
Input current
terminal capacity
I
LN
2
mm
AWG/
A
1)
kcmil
110 (-10 %) - 115 (+10 %) V
230 V AC, three-phase (internal voltage doubler)
2
8
8
7.8
8
8
15.8
8
8
21.9
200 (-10 %) - 240 (+10 %) V
230 V AC, three-phase
2
8
8
3.7
8
8
7.5
8
8
12.9
8
8
12.9
8
8
12.9
8
8
12.9
8
8
19.2
8
8
29.2
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Cross-sectional area/
gauge that should be
used for the power
supply (L1/L, L2/N, L3, PE)
2
mm
AWG/
1)
kcmil
2.5
14
4
10
6
8
1.5
14
1.5
14
2.5
12
2.5
12
2.5
12
2.5
12
4
10
4
8
6 Technical Data
6.4 Cable cross-sections
Output
Cross-sectional area/
current (rated
gauge that should be
operational
used for the motor
current) I
connection (U, V, W, PE)
e
2
A
mm
2.3
1.5
4.3
1.5
5.8
1.5
2.3
1.5
4.3
1.5
7
1.5
7
1.5
7
1.5
7
1.5