3 Installation
3.6 Electrical Installation
3.6.1.7 Cable glands IP66
In the case of units with an IP66 degree of protection, a total of six cable
glands can be installed. The lower section will come with two knockouts for
cable glands that have already been removed and that are intended for the
connections in the power section (Mains ① , Motor ②).
Guide holes are provided for an external braking resistor. In the housing
cover arranged above there are three further guide holes for the feed-through
of control and bus cables.
Make sure that no chips get into the unit when drilling.
Drilling
1
2
PZ 2
4
3
Figure 49:
Bushings
In order to be able to drill further bushings, please loosen the two screws [1]
and remove the housing cover [2].
To drill holes in the metal connection plate, loosen the four screws [3] and
remove the connection plate [4]. You can now drill further holes without
chips getting into the inside of the device.
Installaling the cable glands
Insert a plastic gland into the knockout on the left – which could already have
been punched out at the factory – in order to thread in the power supply
cord. Due to EMC reasons, you should use an metallic EMC cable gland in
the knockout on the right in order to connect the motor cable screen across a
large area and ground it.
91
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com