4.5.3 Keypad usage examples

4.5.3.1 Adjust parameters
Commands
4.5.3.2 Resetting Parameters (RESET)
Commands
Reset to default settings
+
Resetting after a fault
Table 24: Modify parameters
Description
Press the OK button and hold it down for two seconds in order to access the parameter interface.
→ The display will show the parameter that was last used.
Use the ▲ and ▼ buttons to select a parameter.
Press the OK button.
The value of the selected parameter can be changed.
Use the ▲ and ▼ buttons to change the parameter's value.
Press the OK button to confirm the parameter value change.
As soon as the parameter is displayed, the value will have been saved.
Press the OK button and hold it down for two seconds in order to exit the parameter interface (display: "Stop").
Table 25: Resetting parameters (RESET)
Description
Press the ▲ and ▼ and STOP buttons and hold them down for two seconds.
+
→ All parameters will be restored to their default settings.
The display will show
Press the STOP button to reset a fault message.
The display will show
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
P-dEF
.
.
StoP