6.12 Cable routing in the distribution cabinet

• Pre-drill the point where the cable is to be inserted accor-
ding to the cable diameter. Observe internal insulation,
mounting plates and fan!
• Insert existing cables through the cable bulkhead of the
housing.
After inserting the cables, please fill the existing gaps with
mineral wool.
After inserting the cables, set them down and lay them as
shown in the picture below.
Mounting and Operating Instructions Fire-Resistant Cabinet Type DualGuard-S ESF30 January 2021 www.ceag.de

6.13 Pedestal installation

Install the pedestal of the ES enclosure in a manner that
locates the ventilation gap above the pedestal rail (Figure 6).
Ventilation gap
Figure 6

7 Dismantling of the fan unit

at the fire protection enclosure PRIOELEC EHL/ESL
ATTENTION:
The Following installation works have to be done by a qua-
lified electrician!
1. Disconnect the fan unit from the supply voltage taking
care about VDE 0100 230 V mains connection before
beginning to dismantle. Determine freedom from tension.
7 Dismantling of the fan unit
13