Sine Filter - Eaton PowerXL DC1 20 Series Installation Manual

Variable frequency drives
Table of Contents

Advertisement

2.9 Sine filter

Sine filters are connected between a variable frequency drive's output and
the motor. The voltage output by a sine filter will be virtually sinusoidal,
ensuring that:
Conducted and radiated emissions will be reduced (EMC),
Irritating noise levels and motor losses will be reduced,
Potential insulation damage will be minimized, extending the motor's life
as a result.
Sine filters require for the variable frequency drive to modulate
the output voltage with V/Hz control.
In order to meet this requirement, parameter P-60 on DC1-...E1
variable frequency drives needs to be set to a value of 1 (this is
the default setting).
When there is a load-dependent or thermal overload, DC1
variable frequency drives will automatically reduce the carrier
frequency (f
modulation, effective rms value of 4 kHz).
When used with a DX-SIN3... sine filter, the minimum
permissible carrier frequency (f
frequency drive must be set to 8 kHz using parameter P-17.
For the rated sine filters DX-SIN3... for DC1 variable frequency
drives, please refer to the technical data chapter in
→ Section 6.11, "Sine filter", page 179.
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
) to a minimum value of 8 kHz (double
PWM
PWM
2 Engineering
2.9 Sine filter
) on the DC1 variable
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents