6 Technical Data
6.7 Mains chokes
168
DX-LN3...
Figure 84:
Mains chokes DEX-LN3... (three-phase)
Table 41: Assigned mains chokes (three-phase)
Device Type
Input
current
I
LN
A
Mains voltage 230 V
Supply voltage (50/60 Hz) U
U
230 V AC, three-phase / U
e
DC1-322D3...
3.4
DC1-324D3...
5.6
DC1-327D0...
9.5
DC1-32011...
12.1
DC1-32018...
20.9
DC1-32024...
26.4
DC1-32030...
33.3
DC1-32046...
50.1
Mains voltage 400 V
Supply voltage (50/60 Hz) U
U
400 V AC, three-phase / U
e
DC1-342D2...
3.5
DC1-344D1...
5.6
DC1-345D8...
7.5
DC1-349D5...
11.5
DC1-34014...
17.2
DC1-34018...
21.2
DC1-34024...
27.5
DC1-34030...
34.2
DC1-34039...
44.1
DC1-34046...
51.9
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Mains choke, three-phase
(U
max. 500 V +10 %, 50/60 Hz ±10 %)
LN
o
Type (max. 50
C)
200 (-10 %) - 240 (+10 %) V
LN
230 V AC, three-phase
2
DX-LN3-004
DX-LN3-006
DX-LN3-010
DX-LN3-016
DX-LN3-025
DX-LN3-040
DX-LN3-040
DX-LN3-060
380 (-10 %) - 480 (+10 %) V
LN
400 V AC, three-phase
2
DX-LN3-004
DX-LN3-006
DX-LN3-010
DX-LN3-016
DX-LN3-025
DX-LN3-025
DX-LN3-040
DX-LN3-040
DX-LN3-050
DX-LN3-060
o
Type (max. 40
C)
I
e
A
3.7
DX-LN3-004
5.7
DX-LN3-006
9.5
DX-LN3-010
15.2
DX-LN3-016
23.7
DX-LN3-025
38
DX-LN3-040
38
DX-LN3-040
57
DX-LN3-050
3.7
DX-LN3-004
5.7
DX-LN3-006
9.5
DX-LN3-010
15.2
DX-LN3-016
23.7
DX-LN3-025
23.7
DX-LN3-025
38
DX-LN3-040
38
DX-LN3-040
47.5
DX-LN3-050
57
DX-LN3-060
I
e
A
3.9
6
10
16
25
40
40
50
3.9
6
10
16
25
25
40
40
50
60