Eaton PowerXL DC1 20 Series Installation Manual page 109

Variable frequency drives
Table of Contents

Advertisement

3.6.2.11 Control signal terminals IP66
In the case of DC1 variable frequency drives with an IP66 degree of
protection, the plug-in control signal terminals are located under the terminal
cover. In version DC1-...A6SN, the local controls will already be connected.
0
REV
FWD
OFF
PWR
ON
1 2 3 4 5 6 7 8 9 10 11
L1/N L2/N
L3
U
Figure 61:
DC1-...A6S... (connection wired at the factory)
When supplied, the control signal terminals will be connected as follows:
Table 20: Configuration of the control signal terminals
Terminal
Color
1
RD (red)
2
BU (blue)
3
YE (yellow)
5
GN (green)
6
WH (white)
7
BK (black)
When the device is set to its default settings, the setpoint value can be set
using the potentiometer. Meanwhile, the REV – 0 – FWD selector switch can
be used to set the drive's operating direction (counterclockwise rotating field
mode – STOP – clockwise rotating field mode).
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
V
W
1 2 3 4 5 6 7 8 9 10 11
Function
+24 V to FWD/REV selector switch
From selector switch = FWD
From selector switch = REV
+10 V to potentiometer
From potentiometer = f-Set
0 V to potentiometer
3 Installation
3.6 Electrical Installation
BK
WH
GN
YE
BU
RD
105