Dc1-32 - Eaton PowerXL DC1 20 Series Installation Manual

Variable frequency drives
Table of Contents

Advertisement

3 Installation
3.7 Block diagrams
3.7.3 DC1-32..., DC1-34... (in FS1, FS2, FS3)
DC1-32... 3 AC 200 - 240 V
50/60 Hz
DC1-34... 3 AC 380 - 480 V
50/60 Hz
L1/L
DC-
FS2,
FS3
DC+
BR
U
110
Mains voltage U
DC1-32...: 3-phase, 200 (-10 %) - 240 (+10 %) V, 50/60 Hz
DC1-34...: 3-phase, 380 (-10 %) - 480 (+10 %) V, 50/60 Hz
Motor voltage U
Size: FS1, FS2 and FS3 with IP20 degree of protection
L2/N
L3
1
EMC
V
W
PES
3 AC 230/400/460 V
M
3 ~
Figure 65:
Block diagram DC1-32... and DC1-34... in frame sizes FS1, FS2 and FS3
Variable frequency drive with three-phase mains supply voltage and three-
phase motor connection
① Devices with a frame size of FS2 or FS3 allow for DC link coupling
(DC+, DC-) and connecting brake resistors (DC+, BR).
Brake resistor DX-BR3-100 can be inserted underneath the heat sink into
the enclosure and electronically protected against overloads (P-34 = 1).
② DC1-32xxxN..., DC1-34xxxN...: without radio interference suppression
filter
DC1-32xxxF..., DC1-34xxxF...: with built-in radio interference
suppression filter
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
:
LN
: 3-phase, U
= U
2
2
LN
2
3
4
CPU
, 0 - 50/60 Hz (max. 500 Hz)
5
6
7
8
9
10
11
RS485
X1
Modbus RTU
CANopen
OP-Bus

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents