Eaton PowerXL DC1 20 Series Installation Manual page 138

Variable frequency drives
Table of Contents

Advertisement

4 Operational
4.6 Help cards
134
Table 27: Control connections with default settings (help card)
Control signal
Signal
terminal
1
+24 V
2
DI1
3
DI2
4
DI3
5
+10V
6
AI1
7
0 V
8
AO
9
0 V
10
relay
11
When the active enable signal (FWD or REV) is switched off, the
motor will coast to a stop with the default settings.
Table 28: Default settings for basic parameters (help card)
Mode
Designation
parameter
P-01
f-
max
P-02
f-
min
P-03
acc
P-07
U
Motor
P-08
I
Motor
P-09
f
Motor
P-11
V-
Boost
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Description
Control Voltage
Output voltage
Digital Input 1
FWD = clockwise rotating field enable
(U  V  W)
Digital input 2
REV = anticlockwise rotating field enable
(W  V  U)
Digital Input 3
FF1 = Switch from analog setpoint AI1 (control
signal terminal 6) to fixed frequency value f-Fix1 in
parameter P-20 (15 Hz)
Reference voltage
Output voltage
Analog Input 1
Reference voltage: 0 - 10 V = 0 - 50 Hz (Rotating
field frequency)
Reference potential
for +24 V and + 10 V, 0 V = Control signal terminal
9
Analog output
Frequency actual value: 0 - 50 Hz = 0 - 10 V (output
voltage)
Reference potential
for +24 V and + 10 V, 0 V = Control signal terminal
7
Contact N/O
RUN = Run signal (operating signal); closed when
there is an enable signal at DI1 or DI2.
Unit
Description
f-max
Hz
Maximum output frequency; can be set to any
value between f-min (P-02) and the motor's rated
frequency (P-09); maximum setting: 5 x P-09
Min Frequency
Hz
Minimum output frequency, can be set to any
value between 0 and f-max (P-01)
t-acc
s
Acceleration time from stop to rated frequency
(P-09).
Motor Nom
V
Defined rated motor voltage at rated frequency
Voltage
(P-09) = Mains voltage (U
Motor Nom
A
Rated operational current for the DC1 variable
Current
frequency drive. The motor protection function
can be adjusted to match the motor being used by
setting this parameter to the rated motor current
(see example below).
Motor Nom
f
Rated motor frequency (50 Hz) at the rated motor
Frequency
voltage (P-07)
V-Boost
%
Voltage is used to increase the applied motor
voltage at low output frequency, in order to
improve low speed and starting torque.
)
LN