3.6.3 Thermistor connection

106
Motor thermistors and motor thermal switches (Thermoclick) can be
connected to control signal terminal 4 (DI3 = digital input 3) in order to
provide protection against thermal motor overloads.
In this case, parameter P-15 must be used to select the EXTFLT (external
fault) setting for DI3, and parameter P-47 must be set to a value of 6
(Ptc-th).
1 2 3 4 5 6 7 8 9 10 11
T1
T2
U
V
W
PE
M 3 ∼
ϑ
PTC type
≧ 2.5 kΩ trip level
≦ 1.9 kΩ Reset
Figure 62:
Thermistor connection
The thermistors and thermal switches used must be PTC-type units (PTC
characteristic, positive temperature coefficient).
The tripping range must fall within a resistance value range of approximately
2.5 - 3 kΩ, while the reset range must fall within a range of 1.9 - 1 kΩ.