1 DC1 device series
1.6 Voltage categories
26
DC1-1D...
Single-phase mains connection, rated operating voltage of 115 V with
internal voltage doubler
U
= 1~, 110 - 115 V ±10 %, 50/60 Hz
LN
Ie = 2.3 - 5.8 A
Motor: 0.37 - 1.1 kW (230 V, 50 Hz), 1/2 - 1-1/2 HP (230 V, 60 Hz)
FS1, FS2
L1/L
L1
L2/N
N
PE
DC+
Figure 8: DC1-1D...
DC1-12...
Single-phase mains connection, rated operating voltage 230 V
U
= 1~, 200 - 240 V ±10 %, 50/60 Hz
LN
I
= 2.3 - 15.3 A
e
Motor: 0.37 - 4 kW (230 V, 50 Hz), 1/2 - 5 HP (230 V, 60 Hz)
FS1, FS2, FS3
L1/L
L1
L2/N
N
PE
EMC Filter
Figure 9: DC1-12...
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
I
e
Motor
U
V
M
3 ∼
W
BR
Brake Chopper
(FS2)
I
e
Motor
U
V
W
DC+
BR
Brake Chopper
(FS2, FS3)
230 V (U
= 1 ~ 230 V)
LN
M
230 V (U
= 1 ~ 230 V)
LN
3 ∼