3.6.1.1 Terminals in power section for units with IP20 degree of protection
Size
Connection terminals
FS1
PE
⏚
PE
⏚
PES
FS2, FS3
PE
⏚
PE
⏚
PES
Table 6: Terminals (IP20)
L
N
L1/L
L2/N
L3
L1
L2
L3
L1/L
L2/N
L3
U
V
W
M
3
L
N
DC-
L1/L
L2/N
L3
L1
L2
L3
DC-
L1/L
L2/N
L3
DC+
BR
U
V
R
B
M
3
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Description
Connection with single-phase supply voltage:
• DC1-1D... (115 V)
• DC1-12... (230 V)
Note:
Connection to terminal L3 not permissible!
Connection with three-phase supply voltage:
• DC1-32... (230 V)
• DC1-34... (400 V, 480 V)
Motor connection for three-phase motors:
• DC1-1D... (230 V)
• DC1-12... (230 V)
• DC1-32... (230 V)
• DC1-34... (400 V, 460 V)
Connection with single-phase supply voltage (115 V, 230 V):
• DC1-1D (115 V)
• DC1-12 (230 V)
Note:
Connection to terminal L3 not permissible!
DC-: Negative DC link connection if using DC link coupling.
The terminal's plastic cover can be removed if necessary.
Connection with three-phase supply voltage:
• DC1-32... (230 V)
• DC1-34... (400 V, 480 V)
Note:
DC-: Negative DC link connection if using DC link coupling.
The terminal's plastic cover can be removed if necessary.
Motor connection for three-phase motors:
• DC1-1D... (230 V)
W
• DC1-12... (230 V)
• DC1-32... (230 V)
• DC1-34... (400 V, 460 V)
Note:
DC+: Positive DC link connection if using DC link coupling or braking
chopper.
The terminal's plastic cover can be removed if necessary.
BR: Terminal for brake resistor (braking chopper output).
The terminal's plastic cover can be removed if necessary.