Eaton PowerXL DC1 20 Series Installation Manual page 68

Variable frequency drives
Table of Contents

Advertisement

3 Installation
3.3 Mounting
64
When variable frequency drives with internal fans are installed vertically over
each other, an air baffle must be placed between the devices. Failure to do
so may expose the device on top to a thermal overload caused by the guided
air flow (device fan).
Figure 25:
Deflector due to increased circulation caused by device fan
Devices with high magnetic fields (e. g. reactors or
transformers) should not be installed close to the variable
frequency drive.
Table 3: Recommended values for minimum clearances (→ Figure 24)
Size
a
mm
For degree of protection IP20
FS1
50
FS2
50
FS3
50
FS4
50
For degree of protection IP66
FS1
10
FS2
10
FS3
10
FS4
10
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
V
EMC
VAR
V
b
in
mm
in
1,97
33
1,3
1,97
46
1,81
1,97
52
2,05
1,97
52
2,05
0,39
10
0,39
0,39
10
0,39
0,39
10
0,39
0,39
10
0,39
c
mm
in
50
1,97
75
2,95
100
3,94
100
3,94
200
7,87
200
7,87
200
7,87
200
7,87