3 Installation
3.6 Electrical Installation
3.6.2.5 Digital Output (Transistor)
98
When using the device's default configuration, control signal terminal 8 will
be configured as an analog output (AO).
It can be set to work as a digital output instead (DO) with parameter P-25:
Table 13: Control signal terminal 8 (DO)
P-25
Signal
1 = High (+24 V)
0
RUN
1
Ready
2
Actual value =
Setpoint value
3
Error (Fault)
4
f-Out ≧ P-19
5
I-Out ≧ P-19
6
f-Out < P-19
7
I-Out < P-19
10
Not Enable
11
Actual value ≠
Setpoint value
Digital output DO: Accuracy ≧ 1% relative to maximum value
Transistor output DO uses control signal terminal 8 to switch the device's
internal control voltage (+24 V) as a digital signal (1 = High). The maximum
permissible load current is 20 mA.
+ 24 V
8
9
+
Figure 56:
Connecting example (interposing relay with free-wheel diode ETS4-VS3)
Control terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Description
Enable (FWD/REV)
Ready for operation. No fault signal
The output frequency (f-Out) or speed is equal to the setpoint value (REF).
Fault (not ready).
The output frequency (f-Out) is greater than or equal to the value set in P-19
(RO1 upper limit).
The output current (I-Out) is greater than or equal to the value set in P-19 (RO1
upper limit).
The output frequency (f-Out) is less than the value set in P-19 (RO1 upper limit).
The output current (I-Out) is less than the value set in P-19 (RO1 upper limit).
No enable signal (FWD/REV)
The output frequency (f-Out) / speed is not equal to the setpoint value (REF).