3 Installation
3.7 Block diagrams

3.7.1 DC1-1D...

1 AC 110 - 115 V
50/60 Hz
L1/L L2/N
DC-
FS2
DC+
BR
U
V
W
M
3 ~
108
Mains voltage U
Motor Voltage U
0 - 50/60 Hz (max. 500 Hz)
Size: FS1 and FS2 with IP20 degree of protection
1
2
PES
3 AC 230 V
Figure 63:
Block diagram DC1-1D...Nx-...
DC1-1D... variable frequency drives feature a voltage doubler in their internal
DC link. When there is a connected voltage of 1 AC 110 - 115 V, a motor
voltage of up to 3 AC 230 V will be output.
① Devices with a frame size of FS2 allow for DC link coupling (DC+, DC-)
and connecting brake resistors (DC+, BR).
Brake resistor DX-BR3-100 can be inserted underneath the heat sink into the
enclosure and electronically protected against overloads (P-34 = 1).
DC1-1D... variable frequency drives do not feature an internal
radio interference suppression filter. An external radio
interference suppression filter is required for operation as per
EN 61800-3, → Section 6.8, "Radio interference suppression
filter", page 169.
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
: single-phase, 110 (-10 %) - 115 (+10 %) V, 50/60 Hz
LN
: 3-phase, U
= 2 x U
2
2
3
4
5
6
CPU
(voltage doubling),
LN
7
8
9
10
11
RS485
X1
Modbus RTU
CANopen
OP-Bus

Hide quick links: