Mains Chokes - Eaton PowerXL DC1 20 Series Installation Manual

Variable frequency drives
Table of Contents

Advertisement

6.7 Mains chokes

For more information and technical data on DX-LN...
a
mains chokes, please refer to instruction leaflet
IL00906003Z.
DX-LN1...
Figure 83:
DEX-LN1... mains chokes (single-phase)
Table 40: Assigned mains chokes (single-phase)
Device Type
Input
current
I
LN
A
Mains voltage 115 V
Supply voltage (50/60 Hz) U
U
115 V AC, single-phase / U
e
DC1-1D2D3...
7.8
DC1-1D4D3...
15.8
DC1-1D5D8...
21.9
Mains voltage 230 V
Supply voltage (50/60 Hz) U
U
230 V AC, single-phase / U
e
DC1-122D3...
3.7
DC1-124D3...
7.5
DC1-127D0...
12.9
DC1-12011...
19.2
DC1-12015...
29.2
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Mains choke, single-phase
(U
max. 260 V +10 %, 50/60 Hz ±10 %)
LN
o
Type (max. 50
C)
110 (-10 %) - 115 (+10 %) V
LN
230 V AC, three-phase (internal voltage doubler)
2
DX-LN1-009
DX-LN1-018
DX-LN1-024
200 (-10 %) - 240 (+10 %) V
LN
230 V AC, three-phase
2
DX-LN1-006
DX-LN1-009
DX-LN1-018
DX-LN1-024
DX-LN1-032
6 Technical Data
6.7 Mains chokes
o
Type (max. 40
C)
I
e
A
8.1
DX-LN1-009
17.1
DX-LN1-018
22.8
DX-LN1-024
5.5
DX-LN1-006
8.1
DX-LN1-009
17.1
DX-LN1-013
22.8
DX-LN1-024
30.4
DX-LN1-032
I
e
A
8.6
18
24
5.8
8.6
13
24
32
167